| Date |
Text |
| 2017-01-23 13:57:50 | BUILDING PLAN REVIEW |
| | NORTON MUSEUM |
| | W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| | ADD: 1451 S. OLIVE AVE. |
| | CONT: GILBANE |
| | TEL: 561-236-7052 |
| | E-MAIL: [email protected] MICHAEL IZZO |
| | E-MAIL: [email protected] MICHAEL J BEAUMIER |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. JAN. 23/ 2017 |
| | ACTION: DENIED |
| | |
| | NOTICE: ROBERT BROWN HAS WRITTEN A LETTER OF APPROVAL |
| | FOR ALTERNATE MATERIALS AND DESIGN. E-MAIL MAY 04/2015 |
| | AND DESIGN MEETING FROM TUES. JUNE 09/2015 WOULD |
| | REQUIRE ALTERNATE MATERIALS AND DESIGN METHODS, |
| | (PROPOSED COMPLIANCE METHOD), ERIC H. COTE SENIOR |
| | TECHNICAL ADVISOR. |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED UNDER THE STRUCTURAL ONLY PERMIT 16080215, |
| | GEOTECHNICAL REPORT COMPLETED BY ARDAMAN 12/16/2014. |
| | |
| | 4A-H) COMPLIED. |
| | |
| | 4I) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER |
| | AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO |
| | THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014 |
| | ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING |
| | ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS |
| | PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH |
| | 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000 |
| | EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE |
| | IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM |
| | LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN |
| | ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS |
| | PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7. |
| | PLATFORM |
| | LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE |
| | INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER |
| | SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO |
| | SERVE AS A PART OF A MEANS OF EGRESS. |
| | |
| | 4J) PROVISO: 2014FBC-ACCESSIBLITY CODE 703.4.1 HEIGHT |
| | ABOVE FINISH FLOOR OR GROUND. |
| | TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES |
| | (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST |
| | TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE HIGHEST TACTILE CHARACTER. |
| | |
| | |
| | |
| | |
| | |
| | 5A) COMPLIED. |
| | |
| | 5B) 3RD REQUEST. TO CONSIDER THE EXIT PASSAGE WAY |
| | INDICATED AS CORRIDOR 101M TO BE AN EXTENSION OF THE |
| | VERTICAL EXIT, THERE WILL NEED TO HAVE A CUT SECTION |
| | THROUGH THE EXIT ACCESS CORRIDOR (EXIT PASSAGEWAY) EAST |
| | WEST THAT SHOWS THE FLOOR/ CEILING ASSEMBLIES BELOW AND |
| | ABOVE WITH THE RATING OF NOT ONLY THE HORIZONTAL |
| | ASSEMBLIES BUT OF THE VERTICAL SUPPORTING FRAMING. EXIT |
| | PASSAGEWAYS SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711 OR BOTH. SINCE THERE IS |
| | ROOMS EITHER BELOW OR ABOVE THE EXIT PASSAGEWAY WILL |
| | NEED TO HAVE THE SAME RATING AS THE VERTICAL EXIT. THIS |
| | IS NOT CONSIDERED AN EXTENSION TO A STAIRWAY (EXIT |
| | PASSAGEWAY) IN SECTION 1022.3.1 A FIRE DOOR ASSEMBLY |
| | COMPLYING WITH SECTION 716.5 SHALL BE INSTALLED IN THE |
| | FIRE BARRIER TO PROVIDE A MEANS OF EGRESS FROM THE |
| | INTERIOR EXIT STAIRWAY TO THE EXIT PASSAGEWAY. THE DOOR |
| | PROTECTS THE VERTICAL EXIT FROM SMOKE AND FIRE. THIS |
| | REQUEST IS NOT ONLY FROM THE PLAN REVIEWER BUT ALSO THE |
| | BUILDING OFFICIAL ROBERT BROWN. |
| | |
| | 2ND ROUND OF COMMENTS. RESPONSE INDICATES THE ENCLOSURE |
| | THAT CONNECTS THE OCCUPIED SPACE TO THE VERTICAL EXIT |
| | ENCLOSURE IS 2 HOUR RATED. IS THIS 2 HOUR RATING RATHER |
| | THAN HAVE A DOOR SEPARATING THE VERTICAL EXIT FROM THIS |
| | SPACE, ARE YOU LOOKING THIS IS ALTERNATE MATERIALS AND |
| | DESIGN METHODS? IF SO YOU WOULD NEED TO REQUEST SO IN |
| | WRITTEN FORM TO THE BUILDING OFFICIAL. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 104.11 |
| | ALTERNATE MATERIALS, DESIGN AND METHODS OF |
| | CONSTRUCTION. |
| | |
| | 1ST ROUND OF COMMENTS. ON SHEET 0013_LS101M THERE IS A |
| | VERTICAL EXIT STAIR # 5 AND ADJACENT TO THE STAIR |
| | CORRIDOR 101M. THERE IS NO EXIT DOOR SEPARATING THE |
| | VERTICAL EXIT FROM EITHER AN EXIT ACCESS CORRIDOR OR AN |
| | EXIT PASSAGE WAY. HIS USE APPEARS TO BE AN EXIT ACCESS |
| | CORRIDOR MISSING THE DOOR TO THE VERTICAL EXIT. |
| | 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND |
| | RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5. |
| | OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER |
| | THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO |
| | THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM |
| | NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE |
| | ENCLOSURE. |
| | |
| | 6A) COMPLIED. 6B) EXISTING CONDITION. |
| | |
| | 6C-G) COMPLIED. |
| | |
| | 6H) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014 |
| | FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS |
| | VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE |
| | REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10). |
| | |
| | 6I-6J) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | 8A) 2ND REQUEST. PLEASE CLARIFY IN THE F P DRAWINGS, |
| | WHICH SHEET COMPLIANCE CAN BE FOUND. SHEET 0171_A510 |
| | DETAIL DOES PROVIDE A DETAIL FOR THE DRAFT CURTAIN BUT |
| | AGAIN THERE IS NO MENTION OF CLOSELY SPACED SPRINKLERS |
| | IN ACCORDANCE WITH NFPA 13. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET |
| | 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED |
| | PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL |
| | DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER |
| | COMPONENT, SHOW COMPLIANCE WITH FBC-B 603. |
| | |
| | 11&12, A-C) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO |
| | BE SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL |
| | AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR |
| | FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE |
| | PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS |
| | SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B |
| | 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS |
| | ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR |
| | NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR |
| | CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED |
| | IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN |
| | ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE |
| | USED. |
| | |
| | 13 & 14) COMPLIED. |
| | |
| | 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN |
| | EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS |
| | WOULD BE COVERED UNDER THE BUILDING PERMIT. |
| | |
| | 16) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO |
| | WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL |
| | SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL |
| | & PLUMBING DISCIPLES. |
| | |
| | 17) COMPLIED. PRESSURES : SHEETS S008, S009, & S010. |
| | |
| | 18) COMPLIED SEE STRUCTURAL PERMIT: 16080215. |
| | |
| | 19) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | |
| | 20) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL |
| | IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 21) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| | ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| | ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| | IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A |
| | FLORIDA ARCHITECT OR ENGINEER. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | |
| | 22) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 23) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED |
| | WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET |
| | (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| | SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| | 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| | BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| | THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| | |
| | 24) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT |
| | SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT |
| | ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT |
| | ON THE MECHANICAL EQUIPMENT SCREEN. |
| | |
| | 25) 2ND REQUEST TYPE IB & IIA BUILDING REQUIRE FIRE |
| | RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601 |
| | OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS |
| | SECTION OF THE CODE. CLARIFICATION. PLEASE PROVIDE HOW |
| | CODE COMPLIANCE WILL BE ACHIEVED, USING WHAT METHODS |
| | AND MATERIALS. A SPECIFICATION IS JUST THAT, PLEAS |
| | PROVIDE THE DOCUMENTS HOW THE FIRE RATING OF STRUCTURAL |
| | MEMBERS WILL BE ACHIEVED. |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | NEW COMMENT. TYPE IB & IIA BUILDING REQUIRE FIRE |
| | RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601 |
| | OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS |
| | SECTION OF THE CODE. THANK YOU. |
| | |
| | 26 ) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |