| Date |
Text |
| 2016-10-27 14:47:02 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: 2ND REQUEST |
| | |
| | 1.NOT COMPLIED. IT APPEARS THAT THE FIXTURE COUNT IS TO |
| | LOW FOR THE OCCUPANT LOAD. PLEASE PROVIDE A BREAKDOWN |
| | OF FIXTURES REQUIRED AND FIXTURES PROVIDED. PER FBC PL |
| | TABLE 403.1 |
| | USING THE OCCUPANT LOAD FROM THE LIFE SAFETY PAGES THE |
| | REQUIRED NUMBER OF WATER CLOSETS FOR THE WOMEN WOULD BE |
| | 26 TOTAL I CAN ONLY FIND 16 ON THE PLAN. THE REQUIRED |
| | NUMBER OF WATER CLOSETS FOR THE MEN IS 16 I FOUND 12 ON |
| | THE PLAN. IF YOU PROVIDE A BREAKDOWN SHOWING OCCUPANT |
| | LOAD FOR EACH OCCUPANT TYPE AND THE REQUIRED FIXTURE |
| | COUNT AND WHAT IS PROVIDED> IT MIGHT CLARIFY THIS |
| | PROBLEM. |
| | |
| | 3. NOT COMPLIED SHT. P101-104 PLEASE IDENTIFY PIPING |
| | AND SIZES. PERWPB AMEND. TO FBC 107.2.1 |
| | |
| | 6. NOT COMPLIED PROVIDE ISOMETRIC RISER DIAGRAM FOR ANY |
| | NEW STORM WITH SQFT. THAT IS BEING DRAINED ON EACH |
| | PIPE. PER WPB AMEND. TO FBC 107.3.5.1.3(13) |
| | SHT. P505 |
| | A) THEIR ARE PIPES ON THE RISER DIAGRAM THAT END WITH |
| | NO INDICATION OF WHERE THEY GO OR WHAT SIZE PLEASE |
| | IDENTIFY EACH PEACE OF PIPE TO COINCIDE WITH A LOCATION |
| | . |
| | B) PROVIDE SQUARE FOOTAGE AND SLOPE ON EACH SECTION OF |
| | PIPE. |
| | C) SHOW LEVEL AND LOCATION OF EACH ROOF DRAIN. |
| | |
| | 11.NOT COMPLIED SHT A703 DETAIL 3A SHOW GRAB BARS IN |
| | AMBULATORY TOILET COMPARTMENT.PER FBC ACC. 604.8.2.3 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT. P504 THE VENTS ON THE FLOOR SINKS CAN NOT RUN |
| | HORIZONTALLY. PER FBC PL SEC 905.3 VENT CONNECTION TO |
| | DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | |
| | 905.4 VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | |
| | 2.SHT. P121.5-P123.8 WHAT ARE THE SYMBOLS OF THE |
| | CIRCLES WITH THE P50-P58 PLEASE SHOW ON THE PLAN. PER |
| | WPB AMEND. TO FBC 107.2.1 |
| | |
| | 3. ON THE SANITARY RISER DIAGRAM PLEASE PROVIDE A WAY |
| | TO IDENTIFY THE STACKS TO COINCIDE WITH THE FLOOR |
| | PLANS. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 4. PROVIDE A ISOMETRIC RISER DIAGRAM FOR THE KITCHEN |
| | PLUMBING.. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 5. PLEASE EXPAND OR ENLARGE ALL ISOMETRIC DRAWINGS TO |
| | INSURE THAT THEY CAN BE EASILY READ BY THE INSPECTORS |
| | IN THE FIELD. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |