| 2016-10-29 10:24:36 | BUILDING PLAN REVIEW |
| | NORTON MUSEUM |
| | W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| | ADD: 1451 S. OLIVE AVE. |
| | CONT: GILBANE |
| | TEL: 561-236-7052 |
| | E-MAIL: [email protected] MICHAEL IZZO |
| | E-MAIL: [email protected] MICHAEL J BEAUMIER |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. 29/ 2016 |
| | ACTION: DENIED |
| | |
| | NOTICE: ROBERT BROWN IS SUPPOSE TO WRITE A LETTER OF |
| | APPROVAL FOR ALTERNATE MATERIALS AND DESIGN. |
| | |
| | 1) COMPLIED. |
| | |
| | 2) 2ND REQUEST, NOT COMPLETED UNDER THE FOUNDATION/ |
| | STRUCTURE ONLY PERMIT. SHEET 0277_S003 HEADING |
| | FOUNDATIONS INDICATES THERE WAS A GEOTECHNICAL REPORT |
| | COMPLETED BY ARDAMAN 12/16/2014. PLEASE SUBMIT REPORT. |
| | NOTE WHEN SUBMITTED ELECTRONICALLY THE SOILS ENGINEER |
| | WILL NEED TO SUBMIT UNDER AN ELECTRONIC SEAL PER |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS (ELECTRONIC SEALS). |
| | OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT |
| | WILL BE RETAINED AND SCANNED INTO THE SYSTEM. |
| | PLEASE NOTE THE RESPONSE UNDER THE STRUCTURE ONLY |
| | PERMIT WAS THAT A PAPER COPY WAS ALREADY SUBMITTED TO |
| | THE BUILDING DEPARTMENT. I?VE CHECKED WITH THE |
| | ELECTRONIC PLAN REVIEW LIBRARIAN ON THE INCOMING |
| | APPLICATION AND ASSORTED PAPERWORK, THERE IS NO PAPER A |
| | GEOTECHNICAL REPORT COMPLETED BY ARDAMAN 12/16/2014 |
| | WITHIN THE PAPERWORK, THE LIBRARIAN RECORDS SUCH PAPER |
| | DOCUMENTS SO I KNOW TO VERIFY THE REPORT IN PAPER IS |
| | THE SAME REPORT SUBMITTED ELECTRONICALLY AND VERIFY |
| | SIGNATURE ON THE PAPER DOCUMENT. |
| | |
| | 4A-H) COMPLIED. |
| | |
| | 4I) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. WITHIN THE STILLER |
| | AUDITORIUM THERE IS A PLATFORM LIFT TO GAIN ACCESS TO |
| | THE LOWER VIEWING AREA. COMPLIANCE FOR THE FLORIDA 2014 |
| | ACCESSIBILITY CODE FOR VERTICAL ACCESSIBILITY IS BEING |
| | ACHIEVED BY THE PLATFORM LIFT, ACCESS CODE 207.1 AND AS |
| | PART OF A MEANS OF EGRESS IT ALSO HAS TO COMPLY WITH |
| | 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000 |
| | EDITION AND THE 2001 SUPPLEMENT OR SECTION 1007 OF THE |
| | IBC-B 2003 EDITION. IN THE 2003 IBC-B 1007.5. PLATFORM |
| | LIFTS (WHEEL CHAIR) SHALL NOT SERVE AS PART OF AN |
| | ACCESSIBLE MEANS OF EGRESS, EXCEPT WHERE ALLOWED AS |
| | PART OF A REQUIRED ACCESSIBLE ROUTE IN SECTION 1109.7. |
| | PLATFORM |
| | LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE |
| | INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER |
| | SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO |
| | SERVE AS A PART OF A MEANS OF EGRESS. |
| | |
| | 4J) 2ND REQUEST. THE ISSUE IS WITH EXITING, AND AN |
| | ACCESSIBLE EXIT, NOT JUST FOR THIS ROOM BUT EXITS FOR |
| | THE WHOLE OF THE BUILDING. THE DRAWING INDEX INDICATES |
| | SHEET 0260.03_A933_SIGNAGE DETAILS . THE ARE NO DETAILS |
| | FOR ACCESSIBLE SIGNAGE AND FOR DOORS THAT ARE NOT PART |
| | OF AN ACCESSIBLE ROUTE. THE HEIGHT OF SIGNAGE THAT HAS |
| | TACTILE CHARACTERS WITH BRAILLE,2014 FBC-ACCESSIBILITY |
| | CODE 703.4.1. |
| | 703.1 SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL |
| | AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN |
| | WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO |
| | SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE |
| | CHARACTERS, SHALL BE PROVIDED. |
| | 2014 FBC-B 1011.4 RAISED CHARACTER AND BRAILLE EXIT |
| | SIGNS. A SIGN STATING EXIT IN RAISED CHARACTERS AND |
| | BRAILLE AND COMPLYING WITH ICC A117.1 SHALL BE PROVIDED |
| | ADJACENT TO EACH DOOR TO AN AREA OF REFUGE, AN EXTERIOR |
| | AREA FOR ASSISTED RESCUE, AN EXIT STAIRWAY, AN EXIT |
| | RAMP, AN EXIT PASSAGEWAY AND THE EXIT DISCHARGE. |
| | |
| | 1ST ROUND COMMENTS. THE SOME OF THE EXITS DO NOT |
| | INDICATE IF THEY ARE ACCESSIBLE EGRESS DOORWAYS |
| | COMPLYING WITH 2014 FBC-ACCESSIBILITY CODE 207.1 |
| | ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE 2003 |
| | IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE |
| | MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1 |
| | FROM ANY ACCESSIBLE PORTION OF THE SPACE SHALL BE |
| | SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF EGRESS. |
| | THE LIFE SAFETY PLAN IS VAGUE AT BEST. 1027.5 ACCESS TO |
| | A PUBLIC WAY. THE EXIT DISCHARGE SHALL PROVIDE A DIRECT |
| | AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY. |
| | |
| | 5A) COMPLIED. |
| | |
| | 5B) 2ND REQUEST. RESPONSE INDICATES THE ENCLOSURE THAT |
| | CONNECTS THE OCCUPIED SPACE TO THE VERTICAL EXIT |
| | ENCLOSURE IS 2 HOUR RATED. IS THIS 2 HOUR RATING RATHER |
| | THAN HAVE A DOOR SEPARATING THE VERTICAL EXIT FROM THIS |
| | SPACE, ARE YOU LOOKING THIS IS ALTERNATE MATERIALS AND |
| | DESIGN METHODS? IF SO YOU WOULD NEED TO REQUEST SO IN |
| | WRITTEN FORM TO THE BUILDING OFFICIAL. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 104.11 |
| | ALTERNATE MATERIALS, DESIGN AND METHODS OF |
| | CONSTRUCTION. |
| | |
| | 1ST ROUND OF COMMENTS. ON SHEET 0013_LS101M THERE IS A |
| | VERTICAL EXIT STAIR # 5 AND ADJACENT TO THE STAIR |
| | CORRIDOR 101M. THERE IS NO EXIT DOOR SEPARATING THE |
| | VERTICAL EXIT FROM EITHER AN EXIT ACCESS CORRIDOR OR AN |
| | EXIT PASSAGE WAY. HIS USE APPEARS TO BE AN EXIT ACCESS |
| | CORRIDOR MISSING THE DOOR TO THE VERTICAL EXIT. |
| | 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND |
| | RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5. |
| | OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER |
| | THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO |
| | THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM |
| | NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE |
| | ENCLOSURE. |
| | |
| | 6A) COMPLIED. 6B) EXISTING CONDITION. |
| | |
| | 6C-G) COMPLIED. |
| | |
| | 6H) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... 2014 |
| | FBC-ACCESSIBILITY CODE THE USE OF PLATFORM LIFTS IS |
| | VERY LIMITED IN THEIR USE IN NEW CONSTRUCTION. PLEASE |
| | REVIEW THE 2014 FBC-ACCESS. CODE 206.7(1-10). |
| | |
| | 6I-6J) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | 8A) 2ND REQUEST. PLEASE CLARIFY IN THE F P DRAWINGS, |
| | WHICH SHEET COMPLIANCE CAN BE FOUND. SHEET 0171_A510 |
| | DETAIL DOES PROVIDE A DETAIL FOR THE DRAFT CURTAIN BUT |
| | AGAIN THERE IS NO MENTION OF CLOSELY SPACED SPRINKLERS |
| | IN ACCORDANCE WITH NFPA 13. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... SHEET |
| | 0157_A420 DETAIL # 2 INDICATES THE USE OF FULLY ADHERED |
| | PVC ROOFING TO 5/8 INCH THERMAL BARRIER THEN METAL |
| | DECKING. PLEASE IDENTIFY THE 5/8 INCH THERMAL BARRIER |
| | COMPONENT, SHOW COMPLIANCE WITH FBC-B 603. |
| | |
| | 11&12, A-C) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO |
| | BE SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | SHOP DRAWINGS ARE TO BE SUBMITTED FOR THE TYPE OF WALL |
| | AND CEILING SHEATHING/ PANELING AND OR FOAM AND OR |
| | FABRIC FINISHES. THERE MAY BE USE OF A FOAM PANEL THE |
| | PLANS ARE NOT CLEAR, BUT THERE IS FABRIC PANELS AS |
| | SPECIFIED. PLEASE PROVIDE COMPLIANCE WITH FBC-B |
| | 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS |
| | ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR |
| | NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR |
| | CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED |
| | IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN |
| | ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE |
| | USED. |
| | |
| | 13 & 14) COMPLIED. |
| | |
| | 15) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN |
| | EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS |
| | WOULD BE COVERED UNDER THE BUILDING PERMIT. |
| | |
| | 16) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE ALSO |
| | WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME DETAIL |
| | SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL |
| | & PLUMBING DISCIPLES. |
| | |
| | 17) SEMI-COMPLIED. THE SHEETS S008, S009, & S010 ALL |
| | SHOW THE PRESSURES FROM THE WIND STUDY FOR ROOF ZONES |
| | 1, 2 & 3. THESE 3 SHEETS LISTED ABOVE S008 IS THE ONLY |
| | SHEET WHICH SHOWS PRESSURES FOR ROOF ZONES 1, 2 & 3. |
| | THE ROOF ZONES DO NOT PROVIDE PRESSURES FOR ROOF TOP |
| | EQUIPMENT THAT WILL BE ANCHORED TO THE (MWFRS) MAIN |
| | WIND FORCE RESISTING SYSTEM. |
| | PLEASE PROVIDE THE PRESSURES FOR THE DOORS AND WINDOWS |
| | IN WALL ZONES 4 & 5. PLEASE PROVIDE THE PRESSURES FOR |
| | THE WINDOWS AND DOORS AS PER THE WIND STUDY THAT WAS |
| | COMPLETED. FBC-B 1609.1.1DETERMINATION OF WIND LOADS. |
| | EXCEPTION #6 WIND TUNNEL TESTING IN ACCORDANCE WITH |
| | CHAPTER 31 OF ASCE 7. PLEASE NOTE THIS MAY ALSO BE |
| | ACCOMPLISHED UNDER THE STRUCTURE ONLY PERMIT # |
| | 16080215. |
| | 18) 2ND REQUEST. IT SEEMS THE PLANS ARE INCOMPLETE |
| | PLEASE PROVIDE WHERE THE FOUNDATION SCHEDULE, CONCRETE |
| | COLUMN, HOOPS & VERTICAL REBAR AND BEAMS ARE LOCATED, I |
| | COULD NOT FIND THEM IN THE STRUCTURAL SHEETS. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1.1. COMMERCIAL BUILDINGS/ BUILDING: |
| | FOUNDATION SCHEDULE |
| | COLUMN SCHEDULE |
| | BEAM ( CONCRETE/ LINTEL) SCHEDULE |
| | |
| | 19) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | |
| | 20) PROVISO: ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL |
| | IN RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 21) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| | ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| | ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| | IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | IF SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A |
| | FLORIDA ARCHITECT OR ENGINEER. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | |
| | 22) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 23) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED |
| | WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET |
| | (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| | SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| | 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| | BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| | THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| | |
| | 24) PROVISO: DEFERRED SUBMITTAL 107. 3.4.3 TO BE |
| | SUBMITTED AFTER PERMIT ISSUANCE. SHOP DRAWING TO BE |
| | SUBMITTED AND REVIEWED AND STAMPED APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT |
| | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT |
| | SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT |
| | ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT |
| | ON THE MECHANICAL EQUIPMENT SCREEN. |
| | |
| | 25) NEW COMMENT. TYPE IB & IIA BUILDING REQUIRE FIRE |
| | RESISTANCE RATING FOR BUILDING ELEMENTS PER TABLE 601 |
| | OF THE 2014 FBC-B. PLEASE PROVIDE COMPLIANCE WITH THIS |
| | SECTION OF THE CODE. THANK YOU. |
| | |
| | 26 ) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |