| 2016-06-22 10:33:15 | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. SHEET E100/E200- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| | FOR ALL SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE |
| | WILL SUFFICE. |
| | 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| | FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED |
| | TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, |
| | SIGNAGE, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. |
| | 3. PLEASE PROVIDE DETAILS OF ALL ELECTRICAL ROOMS |
| | IMPACTED BY SCOPE OF WORK. FBC 107.3.5 |
| | 4. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC |
| | 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE |
| | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS |
| | AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS |
| | REQUIRED. |
| | 5. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS |
| | FOR FEEDERS AND BRANCH CIRCUITS. |
| | 6. SHEET E-121.8K- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS FOR HOOD SUPPRESSION SYSTEMS. |
| | 7. PROVIDE PHOTOMETRIC FOR ALL INTERIOR AND EXTERIOR |
| | LIGHTING AREAS, MINIMUM LIGHTINGS LEVELS TO BE |
| | MAINTAINED PER FBC. |
| | 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |