| 2016-07-11 07:43:15 | BUILDING PLAN REVIEW |
| | NORTON MUSEUM |
| | W. P. B. PERMIT: 16050912 |
| | ADD: 1451 S. OLIVE AVE. |
| | CONT: GILBANE |
| | TEL: 561-236-7052 |
| | E-MAIL: [email protected] MICHAEL IZZO |
| | [email protected] MICHAEL J BEAUMIER |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JULY 09/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE BE AWARE THIS SCOPE OF WORK REQUIRES A |
| | THRESHOLD INSPECTOR, SEE F.S. THRESHOLD BUILDING FL S. |
| | S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | THE THRESHOLD INSPECTION FORMS WERE SENT TO: |
| | [email protected] MICHAEL IZZO 07/09/2016 7:24 AM |
| | [email protected] MICHAEL J BEAUMIER 07/09/2016 |
| | 7:37 AM |
| | |
| | 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 1D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 1G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 1H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 2) SHEET 0277_S003 HEADING FOUNDATIONS INDICATES THERE |
| | WAS A GEOTECHNICAL REPORT COMPLETED BY ARDAMAN |
| | 12/16/2014. PLEASE SUBMIT REPORT. NOTE WHEN SUBMITTED |
| | ELECTRONICALLY THE SOILS ENGINEER WILL NEED TO SUBMIT |
| | UNDER AN ELECTRONIC SEAL PER 61G15-23.005 PROCEDURES |
| | FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | (ELECTRONIC SEALS). |
| | OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT |
| | WILL BE RETAINED AND SCANNED INTO THE SYSTEM. |
| | |
| | 3) UNDER SHEET 0008_A0004 THE PHASING PLAN THE PLANS |
| | SHOW EXISTING AND THE EXPANSION PLAN. PLEASE PROVIDE |
| | THE EXISTING TOTAL SQUARE FOOTAGE OF THE BUILDING AND |
| | THE TOTAL SQUARE FOOTAGE OF THE BUILDING AT THE END OF |
| | THIS EXPANSION. THIS INFORMATION WILL BE REQUIRED BY |
| | PALM BEACH COUNTY IMPACT FEE OFFICE TO DETERMINE IF |
| | IMPACT FEES ARE DUE. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 4) SHEET 0012_ LS101 VERSES 0097_A101; |
| | |
| | 4A) THE LIFE SAFETY PLAN SEEMS INCOMPLETE, IT APPEARS |
| | THERE ARE EXISTING AREAS OF THE MUSEUM AND PORTIONS |
| | THAT ARE GOING TO BE REMODELED THAT PROVIDE THE SQUARE |
| | FOOTAGE OF THE ROOM AND OCCUPANT LOADS BUT THERE IS NO |
| | ROOM NUMBER TO BE ABLE TO IDENTIFY THE ROOM. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4B) THE LIFE SAFETY PLANS CHARTS SHOWING EXIT CAPACITY |
| | AND OCCUPANT LOADS BUT THE PLAN DOES NOT SHOW |
| | THE EGRESS PATH FOR 50 % OF THE BUILDING. WHERE THE |
| | ROOMS THAT DO SHOW WHAT AMOUNT OF OCCUPANTS THAT ARE |
| | EXITING A ROOM, THEY DO NOT GIVE AN ACCUMULATIVE |
| | OCCUPANT LOAD OF THE EXIT ACCESS CORRIDORS, TO THE |
| | EXIT. DOOR SWINGS CANNOT BE EVALUATED BECAUSE THE PATH |
| | OF TRAVEL AND OCCUPANT LOADS IS UNKNOWN. FBC-B 1005.2 |
| | MINIMUM WIDTH BASED ON COMPONENT. THE MINIMUM WIDTH, IN |
| | INCHES (MM), OF ANY MEANS OF EGRESS COMPONENTS SHALL |
| | NOT BE LESS THAN THAT SPECIFIED FOR SUCH COMPONENT, |
| | ELSEWHERE IN THIS CODE. |
| | |
| | 4C) ROOM 120 THE EMILY & LEONARD LAUDER RESTAURANT |
| | INDICATES 3511 SQ. FT. AND AN OCCUPANT LOAD OF 235 IN |
| | THE LS101 SHEET. WHEREAS IN THE OCCUPANT LOAD CHART |
| | THIS SAME ROOM SHOWS 3,736 SQ. FT. AND AN OCCUPANT LOAD |
| | OF250.EVEN IF YOU FIGURE THE PRIVATE DINING ROOM 121 |
| | THE SQ. FOOTAGE TOTALS UP TO 4286 SQ. FT. THERE IS A |
| | DISCREPANCY IN THE OCCUPANT LOADS FOR BOTH OF THESE |
| | ROOMS. THE PRIVATE DINING ROOM OF 775 SQ. FT. /15= 52 |
| | OCCUPANTS NOT 49. THERE IS A DISCREPANCY IN THE PLANS. |
| | SEE FBC-B TABLE 1004.1.2. |
| | |
| | 4D) WITHIN THIS SAME AREA ROOMS 120 & 121 THE TOTAL |
| | OCCUPANT LOAD 235 + 52 = 287 OCCUPANTS. THE PLANS ONLY |
| | ACCOUNT FOR 167 OCCUPANTS OF THE 287 OCCUPANT LOAD, |
| | THERE ARE 120 OCCUPANTS NOT ACCOUNTED FOR. PLEASE ALSO |
| | NOTE IN THE PRIVATE DINING ROOM 121 LABELED 49 |
| | OCCUPANTS WHICH SHOULD BE 775/15= 52 OCCUPANTS. THE |
| | PLAN SHOWS ALL EXITING THROUGH ONE DOORWAY. PLEASE |
| | REVIEW THE 2014 FBC-B TABLE 1015.1 THE MAXIMUM |
| | ALLOWABLE WITH ONE EXIT IS 49 FOR ASSEMBLY OCCUPANCY. |
| | IF THE OCCUPANCY WAS FIGURED ON THE 775 SQ. FT. AS A |
| | NET @ 15 FT./OCCUPANT THEN THE OCCUPANT LOAD IS 52 |
| | REQUIRING 2 EXITS, NOT PROVIDED. |
| | |
| | 4E) ROOM 118 THE RESTAURANT LOBBY AREA DOES NOT HAVE AN |
| | OCCUPANT LOAD FIGURED IN, THE PLANS DO NOT INDICATE IF |
| | THIS IS A PRE-FUNCTION AREA WHERE THERE WOULD POSSIBLY |
| | BE A QUEUING LINE WHERE AN AREA WOULD BE ROPED OFF WITH |
| | BOLLARDS, THE EGRESS PATH IS UNKNOWN IN THIS CASE? THE |
| | OTHER UNKNOWN IS ROOM 119 SALTMAN CORRIDOR WHERE ARE |
| | THESE OCCUPANTS EXITING. FBC-B 1028.4 THIS SECTION IS |
| | FOR A-1 ASSEMBLY BUT MAYBE A SIMILAR TYPE USE. |
| | |
| | 4F) AREA OF CONCERN WITH STAIR #2 AND EXIT C. THE 1ST |
| | FLOOR PLAN SHOWS A OCCUPANT LOAD OF 135 BEING TAKEN |
| | FROM THE 2ND FLOOR WORST CASE SCENARIO FLOOR DOWN THIS |
| | STAIR. THE EXIT DOOR C IS MAXED OUT AT 340/ 340 |
| | OCCUPANT LOAD. WHEN VIEWING ON SHEET 0014_LS 102 THE |
| | TOTAL OCCUPANT LOAD OF THE 2ND FLOOR OF 463 THERE IS |
| | ONLY 443 OCCUPANTS ACCOUNTED FOR IN THE (4) STAIR |
| | WELLS, STAIR 1 (136 OCC.), STAIR 2 (135) STAIR 4 (68) |
| | AND STAIR 5(104), 136 + 135 + 68 + 104= 443 OCCUPANTS/ |
| | SHORT 20 OCCUPANTS IN THE STAIRWELLS!!!! ALTHOUGH |
| | STAIRWELL # 2 COULD ACCOMMODATE MORE OCCUPANTS THE |
| | LIMITING FACTOR IS AT EXIT DOOR C, IS FULL 340/ 340 |
| | OCCUPANTS. SEE FBC-B 1005.3.2 AND ALSO THE EXCEPTION. |
| | |
| | 4G) CLOAK ROOM NOR CLOSETS SHOW OCCUPANT LOADS. FBC-B |
| | TABLE 1004.1.2. |
| | |
| | 4H) THE COMBINATION FOYERS/ VESTIBULE 110 & 145 SHOW AN |
| | OCCUPANT LOAD OF ONLY 9. THIS AREA MAY ALSO BE A |
| | QUEUING AREA FOR THE A1 THEATER OCCUPANCY. THE PLANS DO |
| | NOT INDICATE IF THIS IS TO BE A PRE-FUNCTION AREA WHERE |
| | THERE WOULD POSSIBLY BE A QUEUING LINE WHERE AN AREA |
| | WOULD BE ROPED OFF WITH BOLLARDS; THE EGRESS PATH IS |
| | UNKNOWN IN THIS CASE? FBC-B 1028.4 THIS SECTION IS FOR |
| | A-1 ASSEMBLY USAGE. |
| | |
| | 4I) WITHIN THE STILLER AUDITORIUM THERE IS A PLATFORM |
| | LIFT TO GAIN ACCESS TO THE LOWER VIEWING AREA. |
| | COMPLIANCE FOR THE FLORIDA 2014 ACCESSIBILITY CODE FOR |
| | VERTICAL ACCESSIBILITY IS BEING ACHIEVED BY THE |
| | PLATFORM LIFT, ACCESS CODE 207.1 AND AS PART OF A MEANS |
| | OF EGRESS IT ALSO HAS TO COMPLY WITH 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE 2000 EDITION AND THE 2001 |
| | SUPPLEMENT OR SECTION 1007 OF THE IBC-B 2003 EDITION. |
| | IN THE 2003 IBC-B 1007.5. PLATFORM LIFTS (WHEEL CHAIR) |
| | SHALL NOT SERVE AS PART OF AN ACCESSIBLE MEANS OF |
| | EGRESS, EXCEPT WHERE ALLOWED AS PART OF A REQUIRED |
| | ACCESSIBLE ROUTE IN SECTION 1109.7. PLATFORM |
| | LIFTS IN ACCORDANCE WITH SECTION 2702 SHALL BE |
| | INSTALLED IN ACCORDANCE WITH ASME A18.1. STANDBY POWER |
| | SHALL BE PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO |
| | SERVE AS A PART OF A MEANS OF EGRESS. |
| | |
| | 4J) THE SOME OF THE EXITS DO NOT INDICATE IF THEY ARE |
| | ACCESSIBLE EGRESS DOORWAYS COMPLYING WITH 2014 |
| | FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS OF EGRESS |
| | SHALL COMPLY WITH THE 2003 IBC SECTION 1007. 2003 IBC-B |
| | 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS REQUIRED BY |
| | SECTION 1014.1 OR 1018.1 FROM ANY ACCESSIBLE PORTION OF |
| | THE SPACE SHALL BE SERVED BY NOT LESS THAN TWO |
| | ACCESSIBLE MEANS OF EGRESS. THE LIFE SAFETY PLAN IS |
| | VAGUE AT BEST. 1027.5 ACCESS TO A PUBLIC WAY. THE EXIT |
| | DISCHARGE SHALL PROVIDE A DIRECT AND UNOBSTRUCTED |
| | ACCESS TO A PUBLIC WAY. |
| | |
| | 5) SHEET 0013_LS101M & 0098_A101M: |
| | |
| | 5A) ON SHEET 0013_LS101M JUST TO THE RIGHT OF CORRIDOR |
| | 101M THERE IS A SMALL ROOM AND DOOR. THERE IS ALSO A |
| | NOTE ON THE PLANS PLEASE CLARIFY ROOM AND DOOR |
| | ARRANGEMENT. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5B) ON SHEET 0013_LS101M THERE IS A VERTICAL EXIT STAIR |
| | # 5 AND ADJACENT TO THE STAIR CORRIDOR 101M. THERE IS |
| | NO EXIT DOOR SEPARATING THE VERTICAL EXIT FROM EITHER |
| | AN EXIT ACCESS CORRIDOR OR AN EXIT PASSAGE WAY. HIS USE |
| | APPEARS TO BE AN EXIT ACCESS CORRIDOR MISSING THE DOOR |
| | TO THE VERTICAL EXIT. |
| | 2014 FBC-B 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND |
| | RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF SECTION 716. SEE TABLE 716.5. |
| | OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER |
| | THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO |
| | THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM |
| | NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE |
| | ENCLOSURE. |
| | |
| | 6) SHEET 0014_LS102 & 0099_A102: |
| | |
| | 6A) BETWEEN THE 2 SHEETS THERE IS A DISCREPANCY IN THE |
| | STAIR IDENTIFICATION NUMBER LS SHEET LIST STAIR AS |
| | STAIR # 01 WHEREAS 0099_A102 ON GRIDLINES X3 5.3X XF-3 |
| | IDENTIFIES THE STAIR AS STAIR # 3 B217. DISCREPANCY IN |
| | PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6B) THE LOWER RIGHT CORNER OF THE PLAN STAIR LABEL BOTH |
| | 1 & 3 HAVE (2) OTHER ROOMS WITHIN THE VERTICAL STAIR |
| | ENCLOSURE. ONE NOT LABELED THE OTHER B215 SECURITY |
| | CLOSET. PLEASE REVIEW THE 2014 FBC-B 1022.4 OPENINGS. |
| | INTERIOR EXIT STAIRWAY AND RAMP OPENING PROTECTIVES |
| | SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| | 716. OPENINGS IN INTERIOR EXIT STAIRWAYS OTHER THAN |
| | UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE |
| | NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM |
| | NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE |
| | ENCLOSURE. ELEVATORS SHALL NOT OPEN INTO INTERIOR EXIT |
| | STAIRWAYS AND RAMPS. |
| | |
| | 6C) THE 2ND FLOOR IS OPEN TO THE 1ST FLOOR IN THE GRAND |
| | HALL AND ADMISSIONS. PLEASE PROVIDE A NORTH / SOUTH |
| | SECTION THROUGH THE CENTER OF THIS AREA. SHEET 0099 THE |
| | 2ND FLOOR SHOWS WHAT APPEARS TO BE A 2 STORY ATRIUM. |
| | THE LIFE SAFETY PLAN 0014 THE 2ND FLOOR SHOWS A SMOKE |
| | PARTITION RATED WALL. THE SHEET 0015_LS 103 THE 3RD |
| | STORY SHOWS A SMOKE RATED PARTITION DOWN TO THE 2ND |
| | FLOOR. IF THIS IS A 3 STORY ATRIUM THEN COMPLIANCE WITH |
| | 404.4 & 404.5. |
| | |
| | 6D) 2014 FBC-B 404.4 FIRE ALARM SYSTEM. A FIRE ALARM |
| | SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 907.2.14. |
| | |
| | 404.5 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL BE |
| | INSTALLED IN ACCORDANCE WITH SECTION 909. |
| | EXCEPTION: SMOKE CONTROL IS NOT REQUIRED FOR ATRIUMS |
| | THAT CONNECT ONLY TWO STORIES. |
| | |
| | 6E) THE OTHER ISSUE IS THE PLANS CALL OUT FOR THE |
| | PARTITIONS ON THE 2ND AND 3RD FLOORS TO BE SMOKE |
| | PARTITIONS. |
| | THE PLANS DO NOT INDICATE THERE WILL BE A SMOKE CONTROL |
| | SYSTEM FBC-B 404.6 EXCEPTION # 3 DIES STATE: |
| | A FIRE BARRIER IS NOT REQUIRED BETWEEN THE ATRIUM AND |
| | THE ADJOINING SPACES OF ANY THREE FLOORS OF THE ATRIUM |
| | PROVIDED SUCH SPACES ARE ACCOUNTED FOR IN THE DESIGN OF |
| | THE SMOKE CONTROL SYSTEM. |
| | |
| | 6F) FOR THE ATRIUM SMOKE CONTROL SYSTEM WILL ALSO NEED |
| | TO COMPLY WITH: FBC-B 404.7 STANDBY POWER. EQUIPMENT |
| | REQUIRED TO PROVIDE SMOKE CONTROL SHALL BE CONNECTED TO |
| | A STANDBY POWER SYSTEM IN ACCORDANCE WITH SECTION |
| | 909.11. |
| | |
| | 6G) FBC-B 404.8 ATRIUM. INTERIOR FINISH. THE INTERIOR |
| | FINISH OF WALLS AND CEILINGS OF THE ATRIUM SHALL BE NOT |
| | LESS THAN CLASS B WITH NO REDUCTION IN CLASS FOR |
| | SPRINKLER PROTECTION. |
| | |
| | 6H)(1) THE PLANS INDICATE THE USE OF A LULA ELEVATOR |
| | FROM CORRIDOR 216 TO THE LIBRARY 220. WITH IN THIS |
| | SPACE THERE IS A SET OF STAIRS. PLEASE IDENTIFY IF THIS |
| | IS NEW CONSTRUCTION OR MODIFICATIONS TO EXISTING |
| | CONSTRUCTION. WITHIN THE 2014 FBC-ACCESSIBILITY CODE |
| | THE USE OF PLATFORM LIFTS IS VERY LIMITED IN THEIR USE |
| | IN NEW CONSTRUCTION. PLEASE REVIEW THE 2014 FBC-ACCESS. |
| | CODE 206.7(1-10). |
| | |
| | 6H)(2) IF ALLOWED AS PART OF A RENOVATION PROJECT THEN |
| | SHOW COMPLIANCE WITH: FLORIDA 2014 ACCESSIBILITY CODE |
| | FOR VERTICAL ACCESSIBILITY IS BEING ACHIEVED BY THE |
| | PLATFORM LIFT, ACCESS CODE 207.1 AND AS PART OF A MEANS |
| | OF EGRESS IT ALSO HAS TO COMPLY WITH 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE 2000 EDITION AND THE 2001 |
| | SUPPLEMENT OR SECTION 1007 OF THE IBC-B 2003 EDITION. |
| | IN THE 2003 IBC-B 1007.5. PLATFORM LIFTS (WHEEL CHAIR) |
| | SHALL NOT SERVE AS PART OF AN ACCESSIBLE MEANS OF |
| | EGRESS, EXCEPT WHERE ALLOWED AS PART OF A REQUIRED |
| | ACCESSIBLE ROUTE IN SECTION 1109.7. PLATFORM LIFTS IN |
| | ACCORDANCE WITH SECTION 2702 SHALL BE INSTALLED IN |
| | ACCORDANCE WITH ASME A18.1. STANDBY POWER SHALL BE |
| | PROVIDED FOR THE PLATFORM LIFTS PERMITTED TO SERVE AS A |
| | PART OF A MEANS OF EGRESS. |
| | |
| | 6I) DISCREPANCY IN IDENTIFICATION OF STAIRS, SHEET |
| | 0014_LS102 IDENTIFIES THE STAIR AS 05 WHERE AS SHEET |
| | 0099_A102 IDENTIFIES THE SAME STAIR AS 1A. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6J) WITHIN THE SAME STAIR IDENTIFIED ABOVE THE TOP |
| | LANDING THERE IS A DOOR NOT IDENTIFIED BUT DOES NOT |
| | HAVE THE 18 INCHES MANEUVERING CLEARANCES ON THE INSIDE |
| | OF THE DOOR. ACCESS. CODE 404.2.4. |
| | |
| | 7) SHEET 0015_LS103 & 0100_A103: |
| | |
| | 7A) AGAIN ON THE LIFE SAFETY SHEET IN THE LOWER RIGHT |
| | HAND CORNER THE STAIRWELL IS LABELED STAIR 1 & 3. |
| | DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 8) GRAND STAIR CASE, STAIR # 2 IS A OPEN STAIR AS |
| | ALLOWED BY FBC-B 1009.3 EXCEPTION # 4. SHEETS 0014 & |
| | 0015 DUE INDICATE THE USE OF DRAFT STOP WITH FIRE |
| | SPRINKLERS, SHEET 0012 THE 1ST FLOOR THERE IS NO |
| | MENTION OF A DRAFT CURTAIN OR FIRE SPRINKLERS. PLEASE |
| | SHOW COMPLIANCE WITH FBC-B 1009.3 EXC. # 4. |
| | |
| | 8A) SHEET 0171_A510 DETAIL DOES PROVIDE A DETAIL FOR |
| | THE DRAFT CURTAIN BUT AGAIN THERE IS NO MENTION OF |
| | CLOSELY SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13. |
| | 8B) SHEET 0166_A503 GRAND STAIR SECTION DETAIL 1 DOES |
| | NOT EVEN SHOW A DRAFT CURTAIN ON THE 3RD FLOOR. |
| | SHOW COMPLIANCE WITH: FBC-B 1009.3 EXC. # 4. IN OTHER |
| | THAN GROUP B AND M OCCUPANCIES, EXIT ACCESS STAIRWAY |
| | OPENINGS ARE NOT REQUIRED TO BE ENCLOSED PROVIDED THAT |
| | THE BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1, |
| | THE FLOOR OPENING DOES NOT CONNECT MORE THAN FOUR |
| | STORIES, THE AREA OF THE FLOOR OPENING BETWEEN STORIES |
| | DOES NOT EXCEED TWICE THE HORIZONTAL PROJECTED AREA OF |
| | THE EXIT ACCESS STAIRWAY, AND THE OPENING IS PROTECTED |
| | BY A DRAFT CURTAIN AND CLOSELY SPACED SPRINKLERS IN |
| | ACCORDANCE WITH NFPA 13. |
| | |
| | 9) SHEET 0228_A806 DOOR SCHEDULE: DOOR C310A MISSING 90 |
| | MIN. LABEL. FBC-B TABLE 716.5 OPENING PROTECTIVES. |
| | |
| | 10) SHEET 0157_A420 DETAIL # 2 INDICATES THE USE OF |
| | FULLY ADHERED PVC ROOFING TO 5/8 INCH THERMAL BARRIER |
| | THEN METAL DECKING. PLEASE IDENTIFY THE 5/8 INCH |
| | THERMAL BARRIER COMPONENT, SHOW COMPLIANCE WITH FBC-B |
| | 603. |
| | |
| | 11)SHEET 0173_ A601 RFC & SHEET 0258_A921 AUDITORIUM |
| | CEILING DETAILS: |
| | |
| | 11A) DETAILS THIS SHEET SHOW A DROPPED DOWN CEILING |
| | FRAMING SYSTEM. THESE DETAILS DO NOT INDICATE THE |
| | MATERIALS OF THE FRAMING IS MADE FROM SIZE NOR SPACING. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 11B) DETAILS THIS SHEET SHOW A DROPPED DOWN CEILING BUT |
| | NO REFERENCE TO THE THICKNESS OF THE CEILING BOARD, |
| | TYPE OF MATERIAL, ETC? 107.3.5.1.1. 11 INTERIOR |
| | FINISHES. 803.11.2 SET-OUT CONSTRUCTION. |
| | |
| | 11C) THERE MAYBE USE OF A FOAM PANEL THE PLANS ARE NOT |
| | CLEAR, BUT THERE IS FABRIC PANELS AS SPECIFIED. PLEASE |
| | PROVIDE COMPLIANCE WITH FBC-B 803.11.2 SET-OUT |
| | CONSTRUCTION. WHERE WALLS AND CEILINGS ARE REQUIRED TO |
| | BE OF FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE |
| | CONSTRUCTION AND WALLS ARE SET OUT OR CEILINGS ARE |
| | DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION |
| | 803.11.1, CLASS A FINISH MATERIALS, IN ACCORDANCE WITH |
| | SECTION 803.1.1 OR 803.1.2, SHALL BE USED. |
| | |
| | 12) SHEET 0173_A601 AUDITORIUM WALLS & SHEET 0255_A918: |
| | |
| | 12A) BUILT OUT WALL DETAILS AS BEFORE COMMENTS, DO NOT |
| | INDICATE THE FRAMING MATERIAL SIZE NOR SPACING OF THE |
| | FRAMING MEMBERS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 12B) ) DETAILS THIS SHEET SHOW A BUILT OUT WALL DETAILS |
| | BUT NO REFERENCE TO THE THICKNESS OF THE WALL BOARD, |
| | TYPE OF MATERIAL, ETC? 107.3.5.1.1. 11 INTERIOR |
| | FINISHES. 803.11.2 SET-OUT CONSTRUCTION. |
| | |
| | 12C) THERE MAYBE USE OF A FOAM PANEL THE PLANS ARE NOT |
| | CLEAR, BUT THERE IS FABRIC PANELS AS SPECIFIED. PLEASE |
| | PROVIDE COMPLIANCE WITH FBC-B 803.11.2 SET-OUT |
| | CONSTRUCTION. WHERE WALLS AND CEILINGS ARE REQUIRED TO |
| | BE OF FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE |
| | CONSTRUCTION AND WALLS ARE SET OUT OR CEILINGS ARE |
| | DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION |
| | 803.11.1, CLASS A FINISH MATERIALS, IN ACCORDANCE WITH |
| | SECTION 803.1.1 OR 803.1.2, SHALL BE USED. |
| | |
| | 13) SHEET 0260_A930 ALL DETAILS SHOW ELECTRICAL FLOOR |
| | BOXES LOCATED IN CONCRETE STRUCTURAL SLABS WITH WOOD |
| | STRINGER BUILT UP FLOORING HEIGHT NOT GIVEN, WITH 2 |
| | LAYERS OF SUB-FLOORING NOT IDENTIFIED. SHOW COMPLIANCE |
| | WITH 2014 FBC-B SECTIONS: |
| | |
| | 805.1 APPLICATION. COMBUSTIBLE MATERIALS INSTALLED ON |
| | OR EMBEDDED IN FLOORS OF BUILDINGS OF TYPE I OR II |
| | CONSTRUCTION SHALL COMPLY WITH SECTIONS 805.1.1 THROUGH |
| | 805.1.3. |
| | EXCEPTION: STAGES AND PLATFORMS CONSTRUCTED IN |
| | ACCORDANCE WITH SECTIONS 410.3 AND 410.4, RESPECTIVELY. |
| | |
| | 805.1.1 SUBFLOOR CONSTRUCTION. FLOOR SLEEPERS, BUCKS |
| | AND NAILING BLOCKS SHALL NOT BE CONSTRUCTED OF |
| | COMBUSTIBLE MATERIALS, UNLESS THE SPACE BETWEEN THE |
| | FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND THE FLOORING |
| | IS EITHER SOLIDLY FILLED WITH NONCOMBUSTIBLE MATERIALS |
| | OR FIREBLOCKED IN ACCORDANCE WITH SECTION 718, AND |
| | PROVIDED THAT SUCH OPEN SPACES SHALL NOT EXTEND UNDER |
| | OR THROUGH PERMANENT PARTITIONS OR WALLS. |
| | |
| | 805.1.2 WOOD FINISH FLOORING. WOOD FINISH FLOORING IS |
| | PERMITTED TO BE ATTACHED DIRECTLY TO THE EMBEDDED OR |
| | FIREBLOCKED WOOD SLEEPERS AND SHALL BE PERMITTED WHERE |
| | CEMENTED DIRECTLY TO THE TOP SURFACE OF |
| | FIRE-RESISTANCE-RATED FLOOR ASSEMBLIES OR DIRECTLY TO A |
| | WOOD SUBFLOOR ATTACHED TO SLEEPERS AS PROVIDED FOR IN |
| | SECTION 805.1.1. |
| | |
| | 14) SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN |
| | EXHAUST HOODS THAT VENT UP THROUGH THE ROOF USUALLY. |
| | NOTE NONE OF THE FLOOR SHEETS SHOW A RATED SHAFT GOING |
| | FROM FLOOR THROUGH TO THE ROOF. 2014 FBC-B 713.1 |
| | GENERAL. THE PROVISIONS OF THIS SECTION SHALL APPLY TO |
| | SHAFTS REQUIRED TO PROTECT OPENINGS AND PENETRATIONS |
| | THROUGH FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES. |
| | 713.4 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL |
| | HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS |
| | WHERE CONNECTING FOUR STORIES OR MORE, AND NOT LESS |
| | THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR STORIES. |
| | THE NUMBER OF STORIES CONNECTED BY THE SHAFT ENCLOSURE |
| | SHALL INCLUDE ANY BASEMENTS BUT NOT ANY MEZZANINES. |
| | SHAFT ENCLOSURES SHALL HAVE A FIRE RESISTANCE RATING |
| | NOT LESS THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED |
| | NOT EXCEED 2 HOURS. SHAFT ENCLOSURES SHALL MEET THE |
| | REQUIREMENTS OF SECTION 703.2. |
| | 713.11 ENCLOSURE AT THE BOTTOM. SHAFTS THAT DO NOT |
| | EXTEND TO THE BOTTOM OF THE BUILDING OR STRUCTURE SHALL |
| | COMPLY WITH ONE OF THE FOLLOWING: |
| | |
| | 15) SHEETS 0269_FS200 & 0270_FS201 BOTH SHOW KITCHEN |
| | EXHAUST HOODS REQUIRE A SEPARATE PERMIT. THE SHAFTS |
| | WOULD BE COVERED UNDER THE BUILDING PERMIT. |
| | |
| | 16) SHEETS 0285_S120.7 & 0286_S120.8 THE WATER FEATURE |
| | ALSO WILL REQUIRE A SEPARATE PERMIT, SHOW THE SAME |
| | DETAIL SHEETS UNDER THE ARCHITECTURAL, STRUCTURAL, |
| | ELECTRICAL & PLUMBING DISCIPLES. |
| | |
| | 17) SHEET S003 PROVIDES THE WIND DESIGN CRITERIA, |
| | PLEASE PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING |
| | AND ASSOCIATED PRESSURES FOR ALL ROOF ZONES 1,2,& 3 AND |
| | WALL ZONES 4 & 5. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | (5) . DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. TABLE |
| | 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & EXPOSURE. |
| | PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING. |
| | |
| | 18) IT SEEMS THE PLANS ARE INCOMPLETE PLEASE PROVIDE |
| | WHERE THE FOUNDATION SCHEDULE, CONCRETE COLUMN, HOOPS & |
| | VERTICAL REBAR AND BEAMS ARE LOCATED, I COULD NOT FIND |
| | THEM IN THE STRUCTURAL SHEETS. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1.1. COMMERCIAL BUILDINGS/ BUILDING: |
| | FOUNDATION SCHEDULE |
| | COLUMN SCHEDULE |
| | BEAM ( CONCRETE/ LINTEL) SCHEDULE |
| | |
| | 19) MISSING PRODUCT APPROVALS. 2010/ 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | |
| | 20) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 21) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY |
| | EITHER A FLORIDA ARCHITECT OR ENGINEER. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. 2014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | |
| | 22) 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 23) FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED |
| | WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET |
| | (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| | SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| | 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| | BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| | THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| | |
| | 24) FBC-B 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL |
| | EQUIPMENT SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN |
| | HEIGHT ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST |
| | POINT ON THE MECHANICAL EQUIPMENT SCREEN. |
| | |
| | 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |