| Notes |
| Date |
Text |
| 2016-05-26 17:10:46 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - NEC 600.5 A 20 AMP DEDICATED BRANCH CIRCUIT REQUIRED. | | | | | | - NEC 600.6 A DISCONNECT REQUIRED EITHER WITHIN SUGHT | | | OR AS A INTERGAL PART | | | | | | - FBC-E C405.2.4 EXTERIOR LIGHTING CONTROLS, LIGHTING | | | NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND | | | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. | | | |
|