| 2016-05-23 12:50:22 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. |
| | |
| | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | (1) AHU #1 - AS PER TRANE DUCULATOR 12"X12" [email protected] |
| | FRICTION LOST PER 100' IS 850 CFM. PLAN IS SHOWING 2000 |
| | CFM DUMPING INTO A 12"X12" DUCT. |
| | AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800 CFM. DESIGN |
| | CFM ON PLANS IS 2000 CFM. |
| | RETURN AIR GRILL ON PLANS IS A200. AS PER CEILINGOUTLET |
| | SCHEDULE RETURMN AIR GRILL SHOULD BE D 2000. |
| | CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS. |
| | ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR. |
| | (AS PER FBC MECHANICAL CODE 2014) |
| | |
| | (2) AHU #2 - PLANS SHOW RETURN AIR IS 1300CFM. TOTAL |
| | SUPPLY AIR IS 2800. |
| | AS PER TRANE DUCULATOR 12"X12" [email protected] FRICTION LOST |
| | PER 100' IS 850 CFM. PLAN IS SHOWING 2800 CFM DUMPING |
| | INTO A 12"X12" DUCT. |
| | CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS. |
| | ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR. |
| | (AS PER FBC MECHANICAL CODE 2014) |
| | |
| | (3) AHU #3 - PROVIDE RETURN AIR. |
| | ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR. |
| | (AS PER FBC MECHANICAL CODE 2014) |
| | |
| | (4) AHU #4 - AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800 |
| | CFM. DESIGN CFM ON PLANS IS 2000 CFM. |
| | DRAWING OF SUPPLY DUCT ON PLANS SHOW PHYSICAL REDUCTION |
| | IN DUCT SIZES BUT DUCT IS IDENTIFIED AS 18" DUCT |
| | THROUGHOUT. |
| | CHECK YOUR CALCULATIONS AND MAKE THE CORRECTIONS. |
| | ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR. |
| | (AS PER FBC MECHANICAL CODE 2014) |
| | |
| | (5) AHU #5 - AHU ON EQUIPMENT SCHEDULE IS SHOWING 1800 |
| | CFM. DESIGN CFM ON PLANS IS 2000 CFM. |
| | PROVIDE ON PLANS RETURN AIR. |
| | SHOW ALL OUTSIDE AIR DUCTS FOR AHU. |
| | ALL SMOKE DETECTORS WILL BE INSTALLED IN RETURN AIR. |
| | (AS PER FBC MECHANICAL CODE 2014) |
| | |
| | CHANGE #2 ON EQUIPMENT SCHEDULE TO ALL SMOKE DETECTORS |
| | WILL BE INSTALLED IN RETURN AIR. (AS PER FBC MECHANICAL |
| | CODE 2014) |
| | |
| | |