| Notes |
| Date |
Text |
| 2016-05-31 17:53:15 | REVISION DENIED FOR BUILDING | | | | | | 1) THE WALL SCHEDULE IS MISSING FROM THE REVISED FLOOR | | | PLAN SHEET A1.1. FBC 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR NEW SIDE | | | ENTRY DOOR THAT HAS BEEN ADDED. DOOR #2 IN THE SCHEDULE | | | TYPE (VIII) A SINGLE OUTSWING GLAZED FRENCH DOOR PGT | | | SERIES 750 REQUIES A PRODUCT APPROVAL THAT HAS BEEN | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD. FBC 107.3.4.1 |
|