| Plan Review Notes For Permit 16050734 |
| Permit Number |
16050734 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-05-24 12:20:36 | 2ND REVIEW: FBC 2014 5TH ED. | | | | | | ACCEPTED AN UPDATED LETTER BY ENGINEER WHICH IS | | | PROPERLY SIGNED AND SEALED. THE LETTER SPEAKS TO REVIEW | | | OF THE PROPOSED REPLACEMENT AS NOT AFFECTING THE | | | LOADING CONDITIONS ON THE TOWER, BUT DOES NOT ADDRESS | | | THE SPECIFIC STRUCTURAL DETAIL OF CONNECTIONS. THE | | | APPLICANT HAS BEEN ADVISED TO PROVIDE ENGINEERED | | | DETAILS OR TO HAVE THE ENGINEER REVIEW THE | | | MANUFACTURERS INSTALLATION METHODS FOR CONSISTENCY WITH | | | WIND CRITERIA. FURTHER THE APPLICANT HAS BEEN ADVISED | | | THAT THE ENGINEER OF RECORD, OR A THIRD PARTY ENGINEER | | | WILL BE REQUIRED TO CERTIFY THE INSTALLATION. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|