| 2016-06-28 07:35:40 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050731 | | | 6/28/16 | | | | | | 1) THE TYPE II EXHAUST FAN SHALL TERMINATE 30" ABOVE | | | THE ROOF SURFACE- SEE SECTION 506.4.2(4). | | | | | | 2) AS PREVIOUSLY REQUESTED PROVIDE AN EQUIPMENT | | | SCHEDULES ON THE PLAN THAT INCLUDES THE MAKE AND MODEL | | | OF THE FAN. THE SUBMITTED NOA HAS MULTIPLE MODELS AND | | | SIZES. PLEASE CIRCLE, HIGHLIGHT, OR OTHERWISE MARK THE | | | MODEL AND SIZE OF THE FAN AND ALL OTHER APPLICABLE | | | DETAILS ON THE NOA. | | | | | | 3) THE EXHAUST APPEARS TO BE TERMINATING LESS THAN 30" | | | FROM THE VERTICAL WALL ABOVE THE ROOF- SECTION | | | 506.4.2(5). PLEASE NOTE THAT IF THE WALL IS ALSO A FIRE | | | WALL BETWEEN TWO PROPERTIES, THE EXHAUST TERMINATION | | | SHALL NOT BE LESS THAN 10' FROM THE WALL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|