| Plan Review Notes For Permit 16050731 |
| Permit Number |
16050731 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-20 16:15:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PERMIT PLAN IS SUBMITTED UNDER THE ARCHITECT AND | | | THE ARCHITECT'STITLE BLOCK AND IS A VIOLATION OF | | | FLORIDA STATUTE AS IS REJECTED. | | | | | | 2) THE SHOP DRAWINGS ARE TO BE SUBMITTED UNDER A | | | QUALIFIED ENGINEER'S REVIEW AND/OR TITLE BLOCK. | | | | | | 3) THE SUBMITTED PLANS ARE TOO SMALL AND UNREADABLE. | | | PROVIDE LARGER AND READABLE PLANS. | | | | | | 4) SHEET M 1 - THE HORIZONTAL VIEW INDCATES INCOMPLETE | | | HOOD VENT COVERAGE AS IT SHOWS IT SHORT ON ONE SIDE OF | | | COVERING THE PROPOSED EQUIPMENT. THE HOOD VENT SHALL | | | COVER ALL EQUIPMENT PER NFPA AND MECHANICAL CODES. | | | | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | | OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|