| Plan Review Notes For Permit 16050730 |
| Permit Number |
16050730 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-19 16:04:46 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050730 | | | 5/19/16 | | | | | | 1) THE NOA SUBMITTED IS FOR AN EXTERIOR WALK-IN COOLER. | | | THE COOLER FOR THE PROJECT IS TO BE INSTALLED IN THE | | | INTERIOR OF THE BUILDING. PLEASE PROVIDE COMPLETE | | | MANUFACTURER'S SPECIFICATIONS FOR THE COOLER INCLUDING | | | A REFRIGERATION EQUIPMENT SCHEDULE. | | | 2) I AM CHALLENGING THE $1900.00 VALUE ON THE | | | APPLICATION PER SECTION 109.3 WPB AMENDMENTS TO THE | | | FBC. PROVIDE AN ACCURATE PRICE THAT INCLUDES LABOR, | | | MATERIALS, AND EQUIPMENT. | | | 3) REMOVE ALL PLAN SHEETS SUBMITTED NOT APPLICABLE TO | | | THE PROPOSED PROJECT. PLEASE NOTE THAT ALL PLAS DRAWN | | | BY AN ARCHITECT OR ENGINEER MUST BEAR THE ORIGINAL | | | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|