| 2016-06-13 18:08:20 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SUBSTRATE IS LISTED AS CONCRETE BLOCK ON THE | | | INSTALLATION SCHEDULE FOR ALL OPENINGS AND THE SPACING | | | MARKED ON THE PRODUCT APPROVAL FOR SOME OF THE STORM | | | PANELS AND ACCORDIONS IS FOR POURED CONCRETE. FBC | | | 107.2.3 THE TABLES ARE SEPARATED INTO POURED CONCRETE | | | AND CONCRETE BLOCK COLUMNS ON BOTH THE ACCORDION | | | SHUTTER AND PANEL PRODUCT APPROVALS. IDENTIFY THE | | | SUBSTRATE THAT YOU WILL BE FASTENING TO AND SELECT THE | | | FASTENER SPACING FOR THE TYPE OF MOUNT FROM THE | | | APPROPRIATE COLUMN. | | | | | | 2) THE GLASS SEPARATION DISTANCE IS MORE THAN 1" FOR | | | BOTH THE PANEL AND THE ACCORDION SHUTTER PRODUCT | | | APPROVALS. PLEASE CORRECT THE INSTALLATION SCHEDULE. | | | FBC R301.1 | | | |
|