| Plan Review Notes For Permit 16050701 |
| Permit Number |
16050701 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-19 16:50:48 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. | | | | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL & 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | (1) PROVIDE INFORMATION ON WHO DREW THE PLANS. ( NAME | | | OF PERSON, SIGNATURE OF PERSON, NAME OF COMPANY, | | | ADDRESS OF COMPANY, CONTRACTOR LICENSE NUMBER ( IF | | | APPLICABLE ) | | | | | | (2) PROVIDE CLEARLY DRAWN PLANS. UNABLE TO CLEARLY SEE | | | SUPPLY AND RETURN DUCT INFORMATION. | | | | | | (3) PROVIDE EQUIPMENT SCHEDULE. (AHU AND CONDENSER) | | | | | | (4) CHECK ALL CFM VALUES. CFM DISTRIBUTION IS NOT AS | | | PER TRANE DUCULATOR. | | | | | | (10" DUCT AT .1% FRICTION LOST IS 400 CFM) PLANS SHOW | | | 10" DUCT GOING TO DISTRIBUTION BOX ON WEST SIDE OF | | | HOME. THE TOTAL CFM YOU SHOW ON THE PLANS OUT OF THAT | | | DISTRIBUTION BOX IS 790 CFM. THIS WILL NOT WORK. | | | | | | (5) DO THE BATHROOMS HAVE EXHAUST? IF THEY DO SHOW ON | | | PLANS. | | | | | | (6) 109.3 BUILDING PERMIT VALUATIONS. | | | | | | PROVIDE VALUATION FOR WORK DONE. APLLICATION SHOWS | | | $0.00. | | | | | | | | | | | | |
|