2016-05-19 16:50:48WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL & 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 (1) PROVIDE INFORMATION ON WHO DREW THE PLANS. ( NAME
 OF PERSON, SIGNATURE OF PERSON, NAME OF COMPANY,
 ADDRESS OF COMPANY, CONTRACTOR LICENSE NUMBER ( IF
 APPLICABLE )
  
 (2) PROVIDE CLEARLY DRAWN PLANS. UNABLE TO CLEARLY SEE
 SUPPLY AND RETURN DUCT INFORMATION.
  
 (3) PROVIDE EQUIPMENT SCHEDULE. (AHU AND CONDENSER)
  
 (4) CHECK ALL CFM VALUES. CFM DISTRIBUTION IS NOT AS
 PER TRANE DUCULATOR.
  
 (10" DUCT AT .1% FRICTION LOST IS 400 CFM) PLANS SHOW
 10" DUCT GOING TO DISTRIBUTION BOX ON WEST SIDE OF
 HOME. THE TOTAL CFM YOU SHOW ON THE PLANS OUT OF THAT
 DISTRIBUTION BOX IS 790 CFM. THIS WILL NOT WORK.
  
 (5) DO THE BATHROOMS HAVE EXHAUST? IF THEY DO SHOW ON
 PLANS.
  
 (6) 109.3 BUILDING PERMIT VALUATIONS.
  
 PROVIDE VALUATION FOR WORK DONE. APLLICATION SHOWS
 $0.00.
  
  
  
  