| 2016-07-14 13:46:16 | 525 OKEECHOBEE BOULEVARD - 9TH FLOOR | | | PERMIT #16050640 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO*****I WILL CHANGE MY REVIEW FROM FAIL TO | | | PASS WITH PROVISO TODAY. IF RBK IS BOTH THE SPRINKLER | | | INSTALLER AND ENGINEER OF RECORD FOR THE SYSTEM, THEY | | | CAN SUBMIT SIGNED/SEALED DRAWINGS UNDER YOUR MASTER | | | PERMIT #16070656 TO ENSURE THE REQUIREMENTS OF THE | | | FLORIDA ADMINISTRATIVE CODE HAVE BEEN MET. | | | | | | REPEAT COMMENT - GENERAL: ENGINEERED FIRE SPRINKLER | | | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL | | | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN | | | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP | | | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION | | | DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE | | | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING | | | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE | | | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS | | | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD | | | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM | | | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP | | | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED | | | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|