| 2016-05-23 11:24:01 | JOB PERMIT NUMBER: 16050640 |
| | JOB ADDRESS: 525 OKEECHOBEE BLVD |
| | WEST PALM BEACH FLORIDA (9TH FLOOR) |
| | DATE: MAY 23 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - BREAKROOM AND COFFEE ROOMS RECEPTACLE OUTLET SHALL |
| | HAVE GFCI PROTECTION NEC 210.8(5)(6) NEAR 6? OF SINKS |
| | AND WET LOCATIONS INDOOR. |
| | - THE APPLICABLE CODE IS THE NEC 2011, THE COVER PAGE |
| | REFERENCES THE NEC 2014 AND E0.1 SHOWS NO CURRENT YEAR. |
| | - ADD THE CODE SECTION NEC 300.22 TO NOTE ?CEILING IS A |
| | COMMON PLENUM NO COMBUSTIBLE MATERIAL ALLOWED.? |
| | - RUNS TO FLOOR BOXES MUST BE IN SEPARATE RACEWAYS AND |
| | ENCLOSURES UNLESS CONDUCTORS PROVIDED WITH SAME VOLTAGE |
| | INSULATION RATING IN ACCORDANCE WITH NEC 300.3(C)(1). |
| | - NEC 410.36(B) SUPPORT OF LUMINAIRES IN SUSPENDED |
| | CEILINGS SHALL BE FASTENED BY MECHANICAL MEANS TO |
| | FRAMING MEMBERS THAT WILL BE SECURELY ATTACHED TO THE |
| | BUILDING STRUCTURE. NEC 300.11 WIRING IN THE FIRE RATED |
| | ASSEMBLIES SHALL BE SUPPORTED BY AN INDEPENDENT SUPPORT |
| | WIRE DISTINGUISHABLE AND PART OF THE CEILING ASSEMBLY. |
| | - RISER DIAGRAM TO INCLUDE NEC 110.16 ARC-FLASH HAZARD |
| | WARNING LABELS AND NEC 110.24 AVAILABLE FAULT CURRENT |
| | MARKINGS, BOTH IDENTIFICATIONS SHALL BE SUITABLE FOR |
| | THE ENVIRONMENT INVOLVED. |
| | - PANEL SCHEDULE NEEDS TO SHOW AIC RATING OF OCPD AND |
| | ELECTRICAL APPARATUS MUST SHOW SCR OF EQUIPMENT. NEC |
| | 110.9, 110.10 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |