| 2016-06-01 14:27:45 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16050640 |
| | ADD: 525 OKEECHOBEE BLVD. 9TH FLOORSUITE # 900 |
| | CONT: HOLT LEE CONSTRUCTION |
| | TEL: 954-725-4881 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 01/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE SUITE NUMBER IS NOT GIVEN ON THE PERMIT |
| | APPLICATION NOR PROVIDED IN THE TITLEBLOCK. 2014 |
| | FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| | PROJECT. |
| | |
| | 2) PLEASE NOTE THIS IS A HIGHRISE BUILDING THAT |
| | REQUIRES FIRE SPRINKLERS PER FBC-B 403.3. THERE IS AN |
| | EXISITNG FIRE SPRINKLER SYSTEM WITHIN THE TENANT SPACE. |
| | IF LESS THAN 50 HEADS NEED TO BE MOVED THE FIRE |
| | SPRINKLER CONTRACTOR CAN DRAW THE PLANS, OTHERWISE THE |
| | FIRE SPRINKLER PLANS NEED TO BE ENGINEERED. WITHIN THE |
| | PLANS SUBMITTED THERRE WAS NO FIRE SPRINKLER PLANS. |
| | PLANS SHALL COMPLY WITH FBC-B 903.2.11.3.1. |
| | |
| | 3A) SHEET A1.1 SHOWS A ASSEMBLY USAGE IN THE RECEPTION |
| | AND CONFERENCE ROOM AREAS. THESE ROOMS WILL HAVE AN |
| | OCCUPANT LOAD OF GREATER THAN 50 REQUIRING (2) MEANS OF |
| | EGRESS. THE DOOR LABELED NUMBER 9 WOULD BE THE 2 ND |
| | REQUIRED MEANS OF EGRESS FROM THIS AREA AND THE DOOR |
| | NEEDS TO SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE |
| | SERVING A ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF |
| | 50 OR MORE PERSONS. FBC-B 1008.1.2. |
| | |
| | 3B) NOTE SHEET E2.1 THE EGRESS DIRECTIONAL LIGHT CLOSE |
| | TO THE BREAK ROOM WILL NEED TO BE RE-DIRECTED TO THE |
| | DOOR # 9 FOR THE 2ND MEANS OF EGRESS FOR THIS AREA. |
| | FBC-B TABLE 1015.1. |
| | |
| | 4) SHEET A1.1 THE DOOR # 9 WILL ALSO NEED TO COMPLY |
| | WITH FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING |
| | ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN |
| | A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| | LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | 5) SHEET A1.1 FILE ROOM 947 & 948 DOES THE FLOOR |
| | LOADING OF THIS FILE ROOM EXCEED THE SAFE FLOOR LIMITS |
| | WITHOUT ADDITIONAL FLOOR FRAMING. THE FLOOR LOADING IN |
| | OFFICE AREAS LIVE LOADS IS BUSINESS AREAS 50 SQ. FT. |
| | WHEREAS FILE ROOMS SHALL BE DESIGNED FOR HEAVIER LOADS |
| | ANTICIPATED USAGE. FBC-B TABLE 1607.1. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |