Plan Review Notes
Plan Review Notes For Permit 16050638
Permit Number 16050638
Review Stop B
Sequence Number 1
Notes
Date Text
2016-05-23 17:21:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC ACCESSIBILITY FIGURE 404.2.4.3, THE MANUAL DOOR
 TO ENTER THE NEW DR SLEEP ROOM APPEARS TO LACK THE 18"
 REQUIRED, PULL SIDE. PLEASE REVISE PLAN TO SHOW THE 18"
 CLEARANCE REQUIRED OR PROVIDE AN ELECTRIC OPENER.
  
  