2016-05-17 18:06:06CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE EQUIPMENT SCHEDULE ( TO INCLUDE BRAND,
 MODEL #, TOTAL CFM, TOTAL BTU)
 (2) PROVIDE HANGING DETAIL OF AIR HANDLER EQUIPMENT
 (3) PROVIDE LOCATION OF CONDENSERS
 (4) PROVIDE CONDENSER TIE DOWN DETAIL
 (5) PROVIDE CFM QUANTITIES OF ALL SUPPLY DROPS.
 (6) PROVIDE O/A CALCULATIONS AND QUANTITIES PER AHU.
  
  