| 2016-05-17 12:41:49 | 500 SOUTH AUSTRALIAN AVENUE - SUITE #700 | | | PERMIT #16050622 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND/OR FIRE | | | ALARM SYSTEM. | | | | | | PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | "FIRE BARRIER-PROTECT ALL OPENINGS." CHARACTERS SHALL | | | BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT | | | RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|