Plan Review Notes
Plan Review Notes For Permit 16050622
Permit Number 16050622
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-20 14:10:47INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A REVISED PANEL LOAD CALCULATION TO
 REFLECT NEW 4TON AC UNIT. FBC 107.3.5
 2. LABEL ALL RECEPTACLES WITHIN 6FT OF SINKS TO BE GFCI
 PROTECTED PER NEC 210.8B7
 3. ALL LOW VOLTAGE SYSTEMS TO BE PERMITTED SEPARATELY,
 A NOTE WILL SUFFICE.
 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  