| Plan Review Notes For Permit 16050622 |
| Permit Number |
16050622 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-20 14:10:47 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A REVISED PANEL LOAD CALCULATION TO | | | REFLECT NEW 4TON AC UNIT. FBC 107.3.5 | | | 2. LABEL ALL RECEPTACLES WITHIN 6FT OF SINKS TO BE GFCI | | | PROTECTED PER NEC 210.8B7 | | | 3. ALL LOW VOLTAGE SYSTEMS TO BE PERMITTED SEPARATELY, | | | A NOTE WILL SUFFICE. | | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|