Plan Review Notes
Plan Review Notes For Permit 16050607
Permit Number 16050607
Review Stop E
Sequence Number 2
Notes
Date Text
2016-07-29 12:54:33SUPERVISOR OVER RIDE.
2016-07-18 17:36:38REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - ALL KITCHEN COUNTERTOP RECEPTACLES MUST BE GFCI
 PROTECTED NEC 210.8 (A)(6) / FBC R E3902.6 ( MARK ON
 PLANS )
  
 - A RECEPTACLE IS SHOWN BEHIND OR ON TOP OF THE
 COUNTERTOP SPACE OCCUPIED BY THE RANGE CLARIFY SPACING
 OR CHANGE THE SYMBOL IF THE INTENT IS A 220 V OUTLET
 FOR THE RANGE. NEC 210.52(C)(4) / FBC R E3901.4.4
  
 - ALL BATHROOM RECEPTACLES SHALL BE GFCI PROTECTED NEC
 210.8(A)(1) / FBC R E3902.1 ( MARK ON PLANS )
  
 - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS
 314 & 315, IF EXISTING MARK ON PLANS.
  
 - ALL NEWLY INSTALLED LIGHTING SHALL BE HIGH EFFICIENCY
 AND IC RATED PLEASE ADD A NOTE. FBC E R404.1
  
 THE ANSWER TO MY INITIAL COMMENTS IN YOUR RESPONSE
 LETTER WERE CORRECT HOWEVER NOTHING WAS REFLECTED ON
 THE PLANS PLEASE ADD THE NOTES IN THE FLOOR PLANS.