| Plan Review Notes For Permit 16050607 |
| Permit Number |
16050607 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-29 12:54:33 | SUPERVISOR OVER RIDE. | | 2016-07-18 17:36:38 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - ALL KITCHEN COUNTERTOP RECEPTACLES MUST BE GFCI | | | PROTECTED NEC 210.8 (A)(6) / FBC R E3902.6 ( MARK ON | | | PLANS ) | | | | | | - A RECEPTACLE IS SHOWN BEHIND OR ON TOP OF THE | | | COUNTERTOP SPACE OCCUPIED BY THE RANGE CLARIFY SPACING | | | OR CHANGE THE SYMBOL IF THE INTENT IS A 220 V OUTLET | | | FOR THE RANGE. NEC 210.52(C)(4) / FBC R E3901.4.4 | | | | | | - ALL BATHROOM RECEPTACLES SHALL BE GFCI PROTECTED NEC | | | 210.8(A)(1) / FBC R E3902.1 ( MARK ON PLANS ) | | | | | | - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS | | | 314 & 315, IF EXISTING MARK ON PLANS. | | | | | | - ALL NEWLY INSTALLED LIGHTING SHALL BE HIGH EFFICIENCY | | | AND IC RATED PLEASE ADD A NOTE. FBC E R404.1 | | | | | | THE ANSWER TO MY INITIAL COMMENTS IN YOUR RESPONSE | | | LETTER WERE CORRECT HOWEVER NOTHING WAS REFLECTED ON | | | THE PLANS PLEASE ADD THE NOTES IN THE FLOOR PLANS. |
|