| 2016-05-23 18:34:37 | JOB PERMIT NUMBER: 16050607 |
| | JOB ADDRESS: 122 WORTH COURT NORTH |
| | WEST PALM BEACH FLORIDA |
| | DATE: MAY 23 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE |
| | THAT IS 12 IN. OR WIDER. RECEPTACLE OUTLETS SHALL BE |
| | INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| | THAN 24 IN. MEASURED HORIZONTALLY FROM A RECEPTACLE |
| | OUTLET IN THAT SPACE. |
| | - NEC 210.52(C)(2)(3) ISLAND & PENINSULAR COUNTERTOP |
| | SPACES. AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH ISLAND & PENINSULAR COUNTERTOP. |
| | - NEC 210.8(A)(6)(7) GFCI PROTECTION REQUIRED IN |
| | KITCHENS WHERE RECEPTACLES SERVE THE COUNTER-TOP |
| | SURFACES AND ALSO WITHIN 6? OF THE OUTER EDGE OF SINKS. |
| | - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE 314 AND |
| | 315. |
| | - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING |
| | UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, |
| | 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER |
| | RESISTANT RECEPTACLES. |
| | - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |