| Plan Review Notes For Permit 16050593 |
| Permit Number |
16050593 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-20 06:31:13 | 1) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE PIPE | | | FROM THE TANKS TO THE FIRST STAGE REGULATOR. | | | 2) THE ANCHORING DETAILS FOR THE LP TANKS FROM STEPHEN | | | WALSH, P.E. SHALL BEAR AN ORIGINAL SEAL AND SIGNATURE | | | PER THE FL. ADMIN. CODE SEC. 61G15-23.001. | | | 3) SHT.P-100 THAT HAS BEEN SUBMITTED IS ILLEGIBLE. | | | 4) SUBMIT TWO SETS OF PLANS FOR REVIEW. CURRENTLY THERE | | | ARE 4 SETS OF PLANS FOR THIS PERMIT. DELETE ALL OLD | | | PLANS. WPB AMEND. TO FBC SEC. 107.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|