| Plan Review Notes For Permit 16050593 |
| Permit Number |
16050593 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-23 10:30:25 | 1) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE PIPE | | | FROM THE TANKS TO THE FIRST STAGE REGULATOR. | | | 2) INDICATE THE DISTANCE, THE TYPE OF PIPE AND THE SIZE | | | OF THE PIPE FROM THE FIRST STAGE REGULATOR TO THE 2ND | | | STAGE REGULATOR. | | | 3) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE PIPE | | | BETWEEN THE FIRST AND SECOND STAGE REGULATOR. | | | 4) PER THE SIZING TABLE THAT HAS BEEN SUBMITTED, THE | | | MAXIMUM BTU LOAD OF A 3/4 INCH PIPE AT 30 FT. IS | | | 336,000 BTU'S. SUBMIT THE CORRECT SIZING TABLE. | | | 5) THE LOCATION OF THE CONTAINER PRESSURE RELIEF AND | | | BUILDING OPENINGS AND SOURCES OF IGNITION SHALL COMPLY | | | WITH TABLE 6.3.8 OF NFPA 58. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|