| Plan Review Notes For Permit 16050574 |
| Permit Number |
16050574 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-08-17 07:14:57 | PROVISO/ DEFERRED SUBMITTAL. SHEET A1.07 ALSO SHOWS 3 | | | FT X 4 FT OPAQUE WOOD ACCESS DOORS W/ COMPACTOR CHUTE | | | BEHIND. PLEASE GIVE ADDITIONAL DETAIL ON THE HARDWARE | | | FOR OPENING THESE DOORS IN COMPLIANCE WITH 2014 | | | FBC-ACCESS. | | | 1A) CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED | | | WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN | | | 308. | | | 1B) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE | | | WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, | | | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED | | | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS. | | | |
|