Plan Review Notes
Plan Review Notes For Permit 16050574
Permit Number 16050574
Review Stop B
Sequence Number 2
Notes
Date Text
2016-07-19 12:25:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050572
 ADD: 7110 OKEECHOBEE BLVD. / PENDING / SITE ENTRY TOWER
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JUNE 16/2016
 ACTION: DENIED
  
 1) THE SITE ADDRESS AND BUILDING ADDRESS ARE STILL
 PENDING UNTIL THE NEW PCN NUMBER IS PUBLISHED BY PALM
 BEACH COUNTY APPRAISERS OFFICE. THE ADDRESS OF THE
 RECREATION/ LEASING BUILDING WILL BE USED FOR THE SITE
 AMENITIES ADDRESS, 7130 OKEECHOBEE BLVD.
  
 2) COMPLIED. ELECTRONIC SIGNATURES. 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 3A) COMPLIED. SHEET A1.07 COMP. THE BUILDING CODE
 INFORMATION LIST THIS COMPACTOR AS FIRE SPRINKLERED
 WITH A 13R SYSTEM. THERE ARE NO FIRE SPRINKLER PLANS IN
 THIS SUBMITTAL. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 3B) SEMI-COMPLIED. NOTE THERE ARE NO STRUCTURAL SHEETS,
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS
 107.3.5.1.1. COMMERCIAL BUILDINGS:
 (8) COMPLIED. STRUCTURAL REQUIREMENTS
  
 WIND DESIGN CRITERIA: DISCREPANCY IN THE PLANS: THE TOP
 CENTER OF THIS SHEET THERE IS A WIND DESIGN 170 VULT
 EXPOSURE B. PLEASE SEE 2014 FBC-B SECTION SURFACE
 ROUGHNESS C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET. THIS
 CATEGORY INCLUDES FLAT OPEN COUNTRY, AND GRASSLANDS.
 THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING
 LOCATED WITHIN SURFACE ROUGHNESS B TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET IN THE
 UPWIND DIRECTION AND A WIDTH GREATER THAN 150 FEET .
 THE OTHER ISSUE IS IN THE STRUCTURAL NOTES THE WIND
 DESIGN CRITERIA IS TAKEN OUT OF ASCE 7-05, 140 MPH THIS
 IS TAKEN FROM THE 2010 FBC-B NOT THE CURRENT CODE.
  
 4-5) COMPLIED.
  
 6) PROVISO/ DEFERRED SUBMITTAL. SHEET A1.07 ALSO SHOWS
 3 FT X 4 FT OPAQUE WOOD ACCESS DOORS W/ COMPACTOR CHUTE
 BEHIND. PLEASE GIVE ADDITIONAL DETAIL ON THE HARDWARE
 FOR OPENING THESE DOORS IN COMPLIANCE WITH 2014
 FBC-ACCESS.
 6A) CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
 6B) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  