| 2016-07-19 12:25:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16050572 |
| | ADD: 7110 OKEECHOBEE BLVD. / PENDING / SITE ENTRY TOWER |
| | CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 16/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE SITE ADDRESS AND BUILDING ADDRESS ARE STILL |
| | PENDING UNTIL THE NEW PCN NUMBER IS PUBLISHED BY PALM |
| | BEACH COUNTY APPRAISERS OFFICE. THE ADDRESS OF THE |
| | RECREATION/ LEASING BUILDING WILL BE USED FOR THE SITE |
| | AMENITIES ADDRESS, 7130 OKEECHOBEE BLVD. |
| | |
| | 2) COMPLIED. ELECTRONIC SIGNATURES. 61G15-23.005 |
| | PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY |
| | TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | |
| | 3A) COMPLIED. SHEET A1.07 COMP. THE BUILDING CODE |
| | INFORMATION LIST THIS COMPACTOR AS FIRE SPRINKLERED |
| | WITH A 13R SYSTEM. THERE ARE NO FIRE SPRINKLER PLANS IN |
| | THIS SUBMITTAL. 107.2.1.3 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 3B) SEMI-COMPLIED. NOTE THERE ARE NO STRUCTURAL SHEETS, |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS |
| | 107.3.5.1.1. COMMERCIAL BUILDINGS: |
| | (8) COMPLIED. STRUCTURAL REQUIREMENTS |
| | |
| | WIND DESIGN CRITERIA: DISCREPANCY IN THE PLANS: THE TOP |
| | CENTER OF THIS SHEET THERE IS A WIND DESIGN 170 VULT |
| | EXPOSURE B. PLEASE SEE 2014 FBC-B SECTION SURFACE |
| | ROUGHNESS C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS |
| | HAVING HEIGHTS GENERALLY LESS THAN 30 FEET. THIS |
| | CATEGORY INCLUDES FLAT OPEN COUNTRY, AND GRASSLANDS. |
| | THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING |
| | LOCATED WITHIN SURFACE ROUGHNESS B TYPE TERRAIN WHERE |
| | THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY |
| | DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR |
| | D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET IN THE |
| | UPWIND DIRECTION AND A WIDTH GREATER THAN 150 FEET . |
| | THE OTHER ISSUE IS IN THE STRUCTURAL NOTES THE WIND |
| | DESIGN CRITERIA IS TAKEN OUT OF ASCE 7-05, 140 MPH THIS |
| | IS TAKEN FROM THE 2010 FBC-B NOT THE CURRENT CODE. |
| | |
| | 4-5) COMPLIED. |
| | |
| | 6) PROVISO/ DEFERRED SUBMITTAL. SHEET A1.07 ALSO SHOWS |
| | 3 FT X 4 FT OPAQUE WOOD ACCESS DOORS W/ COMPACTOR CHUTE |
| | BEHIND. PLEASE GIVE ADDITIONAL DETAIL ON THE HARDWARE |
| | FOR OPENING THESE DOORS IN COMPLIANCE WITH 2014 |
| | FBC-ACCESS. |
| | 6A) CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED |
| | WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN |
| | 308. |
| | 6B) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE |
| | WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |