Plan Review Notes
Plan Review Notes For Permit 16050574
Permit Number 16050574
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-16 16:23:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050572
 ADD: 7110 OKEECHOBEE BLVD. / PENDING / SITE ENTRY TOWER
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JUNE 16/2016
 ACTION: DENIED
  
 1) THE SITE ADDRESS AND BUILDING ADDRESS ARE STILL
 PENDING UNTIL THE NEW PCN NUMBER IS PUBLISHED BY PALM
 BEACH COUNTY APPRAISERS OFFICE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF THE PROJECT,
  
 2) THE PLANS WERE SUBMITTED DIGITALLY, PLEASE NOTE NONE
 OF THE ARCHITECTURAL SHEETS ARE SIGNED FOR ELECTRONIC
 SIGNATURES. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) SHEET A1.07 COMP. THE BUILDING CODE INFORMATION LIST
 THIS COMPACTOR AS FIRE SPRINKLERED WITH A 13R SYSTEM.
 THERE ARE NO FIRE SPRINKLER PLANS IN THIS SUBMITTAL.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3) NOTE THERE ARE NO STRUCTURCAL SHEETS, 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1.1. COMMERCIAL BUILDINGS:
 (8) STRUCTURAL REQUIEMENTS
 WIND DESIGN CRITERIA
  
 4) SHEET A1.01 & A1.07 BOTH SHOW A SLOPED RAMP BUT
 THERE IS NO ELEVATIONS PROVIDED AT THE BOTTOM NOR TOP
 LANDING. PLEASE NOTE THE SLOPE IS INDICATED AT 1:20
 BETWEEN, RAMP SLOPES ARE WITHIN THESE TORANCES FOR NEW
 CONSTRUCTION1:12 AND 1A:20. IF THE SLOPE IS ABOVE THE
 1:20, 1:21 IT IS NO LONGER CONSIDERED A RAMP BUT GRADE.
 AT 1:20 HANDRAILS WILL STILL BE REQUIRED. 2014
 FBC-ACCESS. CODE 405.8 HANDRAILS. RAMP RUNS WITH A RISE
 GREATER THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS
 COMPLYING WITH 505.
  
 5) SHEET A1.07 SHOWS ELEVATIONS AROUND THE DUMPSTER
 ENCLOSURE BUT THERE ARE NONE OF THE RAMP AND THE
 OPENING OF THE COMPACTOR HOPPER SHOWING COMPLIANCE WITH
 REACH RANGES. 2014 FBC-ACCESS. CODE 308 .2 FORWARD AND
 308.3 SIDE REACH RANGES.
  
 6) SHEET A1.07 ALSO SHOWS 3 FT X 4 FT OPAQUE WOOD
 ACCESS DOORS W/ COMPACTOR CHUTE BEHIND. PLEASE GIVE
 ADDITIONAL DETAIL ON THE HARDWARE FOR OPENING THESE
 DOORS IN COMPLIANCE WITH 2014 FBC-ACCESS.
 6A) CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
  
 6B) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  