2016-06-16 15:01:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050572
 ADD: 7110 OKEECHOBEE BLVD. / PENDING / SITE ENTRY TOWER
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JUNE 16/2016
 ACTION: DENIED
  
 1) THE SITE ADDRESS AND BUILDING ADDRESS ARE STILL
 PENDING UNTIL THE NEW PCN NUMBER IS PUBLISHED BY PALM
 BEACH COUNTY APPRAISERS OFFICE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF THE PROJECT,
  
 2) THE PLANS WERE SUBMITTED DIGITALLY, PLEASE NOTE NONE
 OF THE ARCHITECTURAL SHEETS ARE SIGNED FOR ELECTRONIC
 SIGNATURES. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) SHEET A1.10A UNDER THE DESIGN HEADING INDICATES THE
 EXPOSURE AS A "B" EXPOSURE, PLEASE UPDATE PLANS, REVIEW
 SECTION 2014 FBC-B 1609.4.2 SURFACE ROUGHNESS
 CATEGORIES. SURFACE ROUGHNESS C. OPEN TERRAIN WITH
 SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS
 THAN 30 FEET (9144 MM). THIS CATEGORY INCLUDES FLAT
 OPEN COUNTRY, AND GRASSLANDS. THIS SURFACE ROUGHNESS
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE
 ROUGHNESS BTYPE TERRAIN WHERE THE BUILDING IS WITHIN
 100 FEET (30 M) HORIZONTALLY IN ANY DIRECTION OF OPEN
 AREAS OF SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT
 EXTENDS MORE THAN 600 FEET (182.9 M) IN THE UPWIND
 DIRECTION AND A WIDTH GREATER THAN 150 FEET (46 M).
  
 4) SHEET A1.10B THE CUT SECTION THROUGH THE TOWER SHOWS
 WHAT IS ASSUMED AS A 16 INCH TOP BOND BEAM W/ TOP AND
 BOTTOM STEEL, OR MAYBE A LINTEL USED ON THE BOTTOM
 COURSE WITH REBAR IN EACH COURSE, SIZE OF REBAR NOT
 INDICATED, NOR THE LENGTH OF THE CORNER BARS, NO HOOPS,
 STIRRUPS OR HAIRPINS SHOWN SHOW COMPLIANCE WITH . THERE
 IS NOT ENOUGH DETAIL ON THE PLANS. SHOW COMPLIANCE WITH
 FBC-B 2107.3 ACI 530/ASCE 5, SECTION 2.1.7.7, SPLICES
 OF REINFORCEMENT. 7.5.3.1 SHEAR REINFORCEMENT IN
 MASONRY BEAMS.
  
 5) SHEET A1.10B THE CUT SECTION THROUGH THE TOWER SHOW
 COMPLIANCE WITH 2014 FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) BAHAMA STYLE SHUTTERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  