Plan Review Notes
Plan Review Notes For Permit 16050542
Permit Number 16050542
Review Stop B
Sequence Number 2
Notes
Date Text
2016-06-30 14:56:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A SET OF SIGNED AND SEALED TRUSS LAYOUT AND
 DRAWINGS THAT HAVE BEEN APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE TO THE FIELD INSPECTOR PRIOR
 TO INSTALLATION. FBC-R802.1.7.1 THE TRUSS ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE IS REQUIRED ON THE TRUSS
 LAYOUT AND TRUSS DRAWINGS. FACSIMILES ARE NOT
 ACCEPTABLE. THE TRUSS DOCUMENTS THAT WERE SUBMITTED
 HAVE A RUBBER STAMPED SIGNATURE. FAC 61G15-23.002
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY
 FAC61G15-23.002 THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR THE ROOF SHINGLES, WINDOWS, STORM PANELS AND
 EXTERIOR DOORS.
  
 3) THE PLANS SPECIFY NEW SINGLE HUNG WINDOWS IN THE
 SCOPE OF WORK ON SHEET S-1 AND IMPACT CASEMENT WINDOWS
 ON SHEET S-3. CLARIFY AND SUBMIT THE APPROPRIATE
 PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD. FBC 107.2.1 & FAC
 RULE 61G20-3
  
 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 NON-IMPACT RATED CASEMENT WINDOWS. IMPACT PROTECTION OF
 THE GLAZED OPENINGS IS REQUIRED BY FBCR 301.2.1.2.
 SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE STORM
 PANELS ALONG WITH A KEY PLAN AND AN INSTALLATION
 SCHEDULE.
  
 5) SHEET S-1 SPECIFIES FOUR (4) NEW 2-6 X 6-8 IN-SWING
 DOORS AND SHEET S-3 SPECIFIES TWO (2) NEW DOORS, ONE
 OUTSWING 3-0 X 6-8 DOOR AND ONE 2-8 X 6-8 IN-SWING
 DOOR. COORDINATE THE PLANS AND SUBMIT THE APPROPRIATE
 PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED
 IN WRITTING BY THE DESIGNER OF RECORD. FBC 107.2.1 &
 FAC RULE 61G20-3
  
 6)THE ASPHALT SHINGLE ROOF HAS A SLOPE THAT IS LESS
 THAN 4/12 AND REQUIRES A DOUBLE LAYER OF UNDERLAYMENT
 PER FBCR 905.2.2. SUBMIT PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD FOR THE ROOFING MATERIAL THAT WILL BE USED.