Plan Review Notes
Plan Review Notes For Permit 16050542
Permit Number 16050542
Review Stop B
Sequence Number 1
Notes
Date Text
2016-05-25 17:42:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FOLLOWING INSULATION R-VALUES ARE REQUIRED BY
 THE 2014 FBC ENERGY CONSERVATION FOR YOUR PROJECT.
 ATTIC INSULATION TO BE R-30 AND EXTERIOR WALLS TO BE
 R-13 PER SECTION R101.4.3 AND THE COMMON WALL BETWEEN
 THE UNITS SHALL BE R-11 PER SECTION R402.2.13.
  
 2) PROVIDE DETAILS OF THE APPROVED ONE HOUR FIRE
 RESISTIVE ASSEMBLY THAT IS REQUIRED TO SEPARATE THE TWO
 DWELLING UNITS PER FBC-R302.3.
  
 3) SHOW HOW THE RATED WALL WILL COMPLY WITH
 FBC-R302.4.2 FOR MEMBRANE PENETRATIONS OF THE ONE HOUR
 DWELLING SEPARATION WALL.
  
 4) SHOW COMPLIANCE WITH FBC-R 807.1 FOR REQUIRED ATTIC
 ACCESS.
  
 5) SPECIFY THE ROOF SLOPE ON THE PLANS. FBC 107.2.1
  
 6) PROVIDE A SET OF SIGNED AND SEALED TRUSS LAYOUT AND
 DRAWINGS THAT HAVE BEEN APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE TO THE FIELD INSPECTOR PRIOR
 TO INSTALLATION. FBC-R802.1.7.1
  
 7) SHOW THAT THE NEW SOFFIT WILL BE VENTED IN
 COMPLIANCE WITH FBC-R 806.2 MINIMUM VENT AREA.
  
 8) IDENTIFY THE WINDOWS THAT WILL BE REPLACED ON THE
 PLANS AND SPECIFY THEIR SIZES. FBC 107.2.1
  
 9) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 ROOFING MATERIALS AND SINGLE HUNG WINDOWS.
  
 10) PER THE 2014 FBC EXISTING BUILDING SECTION 708.1.1,
 WHEN MORE THAN 25% OF THE TOTAL ROOF AREA OR ROOF
 SECTION IS BEING REPLACED, THEN THE ENTIRE ROOF SYSTEM
 IS REQUIRED TO BE REPLACED TO MEET CODE.
  
2016-05-19 16:06:35DETERMIONE IF RE-ROOFING IS PART OF THIS SCOPE IF SO,
 AND UPON APPROVAL, REVOKE OLD RE-ROOF PERMIT, 03070942,
 SAK