2016-06-01 09:03:15REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 - NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
  
 - NEC 210.52(E)(3) PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE THE DWELLING UNIT SHALL HAVE AT LEAST ONE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE PORCH. OUTDOOR
 RECEPTACLE SHALL BE GFCI PROTECTED IN ACCORDANCE WITH
 210.8(A)