| Plan Review Notes For Permit 16050541 |
| Permit Number |
16050541 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-01 09:03:15 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | - NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE | | | SUPPORT OF CEILING FANS SHALL BE MARKED BY THE | | | MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE | | | THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT | | | PADDLE FANS HEAVIER THAN 70 LBS. | | | | | | - NEC 210.52(E)(3) PORCHES THAT ARE ACCESSIBLE FROM | | | INSIDE THE DWELLING UNIT SHALL HAVE AT LEAST ONE OUTLET | | | INSTALLED WITHIN THE PERIMETER OF THE PORCH. OUTDOOR | | | RECEPTACLE SHALL BE GFCI PROTECTED IN ACCORDANCE WITH | | | 210.8(A) |
|