| Plan Review Notes For Permit 16050541 |
| Permit Number |
16050541 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-26 08:12:31 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE | | | ROOFING MATERIALS. | | | | | | 2) IF THE PRODUCT APPROVALS FOR THE ROOFING REQUIRES | | | ENHANCED FASTENING IN THE PERIMETER AND CORNER AREAS, | | | SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS. | | | | | | 3) THE EDITIONS OF SEVERAL CODES AND STANDARDS ARE | | | LISTED ON SHEET 1.1 ARE INCORRECT. THESE ARE THE | | | CORRECT EDITIONS: 2011 NFPA-70 (NEC), NFPA 101 (2012 | | | EDITION) AND THE FIRE PREVENTION CODE (2014). FBC-R | | | CHAPTER 46. | | | |
|