2016-06-15 14:01:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF FLOOR PLANS OF THE SINGLE FAMILY
 RESIDENTIAL STRUCTURE SHOWING THE LOCATIONS OF THE
 PROPOSED WORK. FBC 107.2.1
  
 2) PROVIDE TWO COPIES OF A ROOF FRAMING PLAN AND
 SPECIFY WHICH TRUSSES WILL BE RETROFITTED WITH NEW
 HURRICANE STRAPS. FBC 107.2.1
  
 3) PROVIDE ENGINEERED DESIGN FOR ROOF TO WALL TRUSS
 CONNECTIONS OR COMPLY WITH THE PRESCRIPTIVE RETROFIT
 SOLUTIONS PROVIDED IN FBC EXISTING BUILDINGS SECTIONS
 708.8.1.1 THROUGH 708.8.1.7.
  
 4) SHOW COMPLIANCE WITH FBC-R314 FOR SMOKE ALARMS AND
 R-315 FOR CARBON MONOXIDE ALARMS.
  
 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 NEW FIREPLACE. FBC 107.2.1
  
 7) THERE ARE TWO ELECTRICAL SUB PERMIT APPLICATIONS
 (#16050521 & #16051023) FROM DIFFERENT CONTRACTORS FOR
 THE ELECTRICAL WORK ON THIS PROJECT. THERE CAN ONLY BE
 ONE ELECTRICAL SUB FOR THIS SCOPE OF WORK. CHOOSE THE
 ONE YOU WILL USE AND CANCEL THE OTHER PERMIT.
  