| 2016-05-12 11:00:49 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | ELEVATION CERTIFICATE DATED 4/27/2016 PREPARED BY LUIS |
| | J. ORTIZ, BASELINE ENGINEERING & LAND SURVEYING |
| | |
| | 1. A9 (A), SQUARE FOOTAGE OF GARAGE IS 460 SF, BUT THE |
| | BUILDING PERMIT PLAN STATES THAT THE GARAGE IS 565 SF. |
| | REVISE OR CLARIFY. |
| | |
| | 2. A9 (D), NO FLOOD OPENINGS WERE INSTALLED. GARAGE |
| | FLOOR ELEVATION (C2 E) IS LESS THAN THE MINIMUM |
| | REQUIRED. ELEVATION CERTIFICATE SHOWS THE GARAGE AT |
| | 7.28', MINIMUM REQUIREMENT IS 7.5'. SEE THE SITE PLAN |
| | PREPARED BY LUIS ORTIZ WHICH SHOWS PROPOSED GARAGE FFE |
| | AT 7.5', TWO STORY CBS FFE OF 8.75. AS THE GARAGE |
| | FINISHED FLOOR DOES NOT MEET THE FREEBOARD REQUIREMENT, |
| | A REVISION IS REQUIRED. THE REVISION SHOULD INCLUDE |
| | FLOOD VENTS IN THE GARAGE AND, IF ENGINEERED FLOOD |
| | VENTS ARE PROPOSED, PRODUCT APPROVAL OR ENGINEERING |
| | SUBMITTED. |
| | |
| | 3. THE PLANS SHOW A WATER HEATER AND CENTRAL VACUUM IN |
| | THE GARAGE, BUT THE GARAGE FINISHED FLOOR IS LOCATED AT |
| | LESS THAN 7.5'. THE EQUIPMENT IS TO BE ELEVATED TO A |
| | MINIMUM OF 7.5' (SEE PLAN REVIEW NOTES AND REDLINES ON |
| | SHEET E1). |
| | |
| | SEE ITEM C2E. THE ELEVATION CERTIFICATE SHOWS THE |
| | LOWEST ELEVATION OF MACHINERY OR EQUIPMENT AT 8.80', |
| | NOTE STATES THAT THIS IS THE AC PAD. CLARIFY THE |
| | ELEVATION OF THE CENTRAL VAC AND WATER HEATER. PHOTOS |
| | OF ALL EQUIPMENT IS TO BE INCLUDED WITH THE ELEVATION |
| | CERTIFICATE. |
| | |
| | 4. PLEASE HAVE THE SURVEYOR EXPLAIN THE DISCREPANCY |
| | BETWEEN THE "BUILDING UNDER CONSTRUCTION" ELEVATION |
| | CERTIFICATE WHICH SHOWS THE GARAGE FINISHED FLOOR AT |
| | 7.97, BUT THE FINISHED CONSTRUCTION ELEVATION |
| | CERTIFICATE SHOWS THE GARAGE FINISHED FLOOR AT 7.28. |
| | THIS SIGNED AND SEALED ELEVATION CERTIFICATE IS DATED |
| | 11/3/2015. IF BOTH ELEVATION CERTIFICATES ARE ACCURATE, |
| | PLEASE HAVE THE SURVEYOR PROVIDE THIS INFORMATION IN |
| | WRITING. THE BUILDING INSPECTOR RELIED ON THIS |
| | INFORMATION TO CONFIRM THAT THE FINISHED FLOOR COMPLIED |
| | WITH THE NFIP REQUIREMENTS. IT IS NOT CLEAR HOW THE |
| | GARAGE COULD DROP 8" AFTER CONCRETE WAS POURED. AN |
| | EXPLANATION WOULD BE APPRECIATED TO AVOID THIS |
| | SITUATION IN THE FUTURE. |
| | |
| | 5. THE NEW ELEVATION CERTIFICATE IS NOW ON THE FEMA |
| | WEBSITE, PLEASE USE THE CURRENT FORM: |
| | HTTP://WWW.FEMA.GOV/MEDIA-LIBRARY/ASSETS/DOCUMENTS/160 |
| | |
| | 6. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE, ALL |
| | EQUIPMENT RELATIVE TO FFE OR GRADE, AND ALL FLOOD VENTS |
| | (IF APPLICABLE) ARE REQUIRED PER CRS ACTIVITY RA3. THIS |
| | MAY BE PROVIDED AS PART OF THE ELEVATION CERTIFICATE OR |
| | BY THE CONTRACTOR. |
| | |
| | 7. SECTION D, THE BOX MARKED "NO" IS CHECKED REGARDING |
| | THE SOURCE OF LATITUDE/LONGITUDE. IN FLORIDA, ONLY A |
| | PROFESSIONAL LAND SURVEYOR CAN COMPLETE AN ELEVATION |
| | CERTIFICATE. AS THE LAT/LONG COORDINATES WERE PROVIDED |
| | BY THE SURVEYOR, PLEASE REVISE TO CHECK THE BOX "YES." |
| | |
| | 8. OWNER IS SHOWN AS "RICHARD RODMAN" BUT OUR RECORDS |
| | SHOW THE OWNER AS "KENNEDY COLLIN BUILDERS LLC". PLEASE |
| | CORRELATE. |
| | |
| | |
| | |
| | |
| | |
| | |