| Plan Review Notes For Permit 16050497 |
| Permit Number |
16050497 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-16 07:59:38 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050497 | | | 5/16/16 | | | | | | 1) THE PERMIT VALUE OF $4800.00 IS TOO LOW. VALUE IS | | | BASED ON LABOR, MATERIALS, AND EQUIPMENT- SECTION 109.3 | | | WPB AMENDMENTS TO THE FBC. | | | 2) PROVIDE A COMPLETE NOA OR PRODUCT APPROVAL FOR THE | | | AC STANDS- ONLY ONE SHEET HAS BEEN SUBMITTED. PLEASE | | | NOTE SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED | | | FOR ALL ROOFTOP EQUIPMENT INSTALLATIONS- SECTION | | | 301.15. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE ICE | | | MACHINE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|