2016-06-07 08:22:132ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050462
 6/7/16
  
 1) THE OUTDOOR AIR CALCULATIONS ARE NOT IN COMPLIANCE
 WITH TABLE 403.3 WHICH REQUIRES 7.5 CFMS PER PERSON AND
 .12 CFM PER SF. FOR RETAIL SPACES. THE RATE IS
 CALCULATED AT 15 PERSONS PER 1000 SF. PLEASE REVISE THE
 CALCULATIONS.
  
 2) PLEASE INDICATE HOW OUTSIDE AIR IS BEING PROVIDED TO
 THE NEW RETAIL SPACES- NO OUTSIDE AIR DUCTS ARE SHOWN
 ON THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER