| Plan Review Notes For Permit 16050462 |
| Permit Number |
16050462 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-07 08:22:13 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050462 | | | 6/7/16 | | | | | | 1) THE OUTDOOR AIR CALCULATIONS ARE NOT IN COMPLIANCE | | | WITH TABLE 403.3 WHICH REQUIRES 7.5 CFMS PER PERSON AND | | | .12 CFM PER SF. FOR RETAIL SPACES. THE RATE IS | | | CALCULATED AT 15 PERSONS PER 1000 SF. PLEASE REVISE THE | | | CALCULATIONS. | | | | | | 2) PLEASE INDICATE HOW OUTSIDE AIR IS BEING PROVIDED TO | | | THE NEW RETAIL SPACES- NO OUTSIDE AIR DUCTS ARE SHOWN | | | ON THE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|