| Plan Review Notes For Permit 16050462 |
| Permit Number |
16050462 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-16 11:00:32 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050462 | | | 5/16/16 | | | | | | 1) THE REVISED PLANS DO NOT INDICATE HOW OUTDOOR AIR IS | | | BEING PROVIDED TO THE NEW AC SYSTEMS: | | | A) REFER TO TABLE 403.3 AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR EACH NEW SPACE. | | | B) SHOW HOW THE REQUIRED AIR IS BEING SUPPLIED TO THE | | | OCCUPANCIES- TYPE AND SIZE OF O/A DUCTS, AND LOCATIONS | | | OF THE AIR INLETS. | | | C) PROVIDE A MEANS OF AUTOMATIC CONTROL FOR THE SHUTOFF | | | DAMPERS- SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|