2016-05-16 11:00:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050462
 5/16/16
  
 1) THE REVISED PLANS DO NOT INDICATE HOW OUTDOOR AIR IS
 BEING PROVIDED TO THE NEW AC SYSTEMS:
 A) REFER TO TABLE 403.3 AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR EACH NEW SPACE.
 B) SHOW HOW THE REQUIRED AIR IS BEING SUPPLIED TO THE
 OCCUPANCIES- TYPE AND SIZE OF O/A DUCTS, AND LOCATIONS
 OF THE AIR INLETS.
 C) PROVIDE A MEANS OF AUTOMATIC CONTROL FOR THE SHUTOFF
 DAMPERS- SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER