| Plan Review Notes For Permit 16050446 |
| Permit Number |
16050446 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-15 08:43:03 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | PROVISO COMMENTS: | | | | | | 1. PLEASE UPDATE ALL REFERENCES TO REFLECT CURRENT | | | BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION | | | FAMILY, NEC 2011. | | | 2. PROVIDE A NOTE TO COMPLY WITH THE FBC EC | | | CODE-R404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS. | | | 50% OLD CODE | | | 3. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|