2016-06-23 12:57:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET LS 1 & A 1 - THE PLAN INDICATES ONLY ONE
 HANDRAIL ON THE WALL SIDE OF THE REAR STAIR.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 THE EXCEPTIONS DO NOT APPLY TO YOUR INSTALLATION.
  
 PLEASE PROVIDE A HANDRAIL TO THE OPPISITE SIDE OF THE
 STAIR. THE INSTALLATION WILL BE VERIFIED ON FIRE
 INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  