| Plan Review Notes For Permit 16050444 |
| Permit Number |
16050444 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-23 12:57:08 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) SHEET LS 1 & A 1 - THE PLAN INDICATES ONLY ONE | | | HANDRAIL ON THE WALL SIDE OF THE REAR STAIR. | | | | | | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS | | | | | | 7.2.2.4 GUARDS AND HANDRAILS. | | | 7.2.2.4.1 HANDRAILS. | | | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON | | | BOTH SIDES, | | | UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR | | | 7.2.2.4.1.6. | | | | | | THE EXCEPTIONS DO NOT APPLY TO YOUR INSTALLATION. | | | | | | PLEASE PROVIDE A HANDRAIL TO THE OPPISITE SIDE OF THE | | | STAIR. THE INSTALLATION WILL BE VERIFIED ON FIRE | | | INSPECTIONS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|