Plan Review Notes
Plan Review Notes For Permit 16050444
Permit Number 16050444
Review Stop G
Sequence Number 1
Notes
Date Text
2016-05-31 06:39:211) SHOW THE DISTANCE OF THE LP TANK FROM THE BUILDING
 WALL. COMPLY WITH NFPA 58 SEC.6.3.2.3 - NO PART OF AN
 UNDERGROUND OR MOUNDED ASME CONTAINER
 SHALL BE LESS THAN 10 FT (3 M) FROM A BUILDING OR LINE
 OF ADJOINING PROPERTY THAT CAN BE BUILT UPON
 2) SHOW THE DISTANCE OF THE LP TANK TO THE
 DRIVEWAY.INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC
 VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION
 SHALL BE PROVIDED WITH
 VEHICULAR BARRIER PROTECTION FOR THE CONTAINER?S
 FITTING HOUSING, COMPLY WITH NFPA 58 SEC.6.6.6.1 (C) &
 (E) - THE INSTALLATION OF A BURIED CONTAINER SHALL
 INCLUDE PROTECTIONFOR THE CONTAINER AND PIPING AGAINST
 PHYSICAL DAMAGE
 FROM VEHICULAR TRAFFIC.
 3) SUBMIT COMPLETE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATIONN MANUAL FOR REVIEW. THE
 GENERATOR SHALL BE UL 2200 LISTED AND BE INSTALED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37. 2014 FBC-FUEL GAS SEC.616.1.
 4) THE GAS SHALL BE SUBMITTED AS A SEPARATE PERRMIT.
 5) SUBMIT DETAILS AS TO HOW THE LP TANK WILL BE
 ANCHORED TO PREVENT FLOTATION. NFPA 58 SEC. 6.6.1.6.
 6) GAS SHALL BE DONE UNDER A SEPARATE PERMIT.
  