2016-05-19 16:52:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET D 1 - THERE IS NO INDICATION OF REVIEW OF
 COMPLAINCE WITH THE FLORIDA FIRE PREVENTION CODE.
 PLEASE ENSURE COMPALINACE AND PROVIDE A NOTE:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 2) SHEET D 1 & A 2 - IS THIS A MIXED OR SEPARATED
 OCCUPANCY? THE AREA OF THE STORAGE AND THE AREA IN THE
 FRONT IS BUISNESS/ASSEMBLY AND IS REQUIRED TO BE
 SEPARATED BY A 2 HOUR FIRE RATING. PLEASE
 EXPLAIN/JUSTIFY AND/OR PROVIDE SEPARATION PER NFPA 101,
 CHAPTER 6, 6.1.14.4.1.
  
 3) SHEET A 2 - THE DOOR SCHEDULE DOES NOT INDICATE THE
 TYP OF HARDWARE FOR DOORS INDICATED AS # 2. PLEASE
 PROVIDE HARDWARE COMPLIANT WITH NFPA 101, CHAPTER 7,
 MEANS OF EGRESS, 7.2
  
 4) SHEET LS 1 - THE REAR EEXIT DOES NOT INDCATE A
 DISCHARGE TO A PUBLIC WAY. THE AREA IS FENCED. THIS
 DOES MEET THE REQUIRED EXTING FROM THE STURCTURE PER
 NFPA 101, CHAPTER 7, MEANS OF EGRESS, 7.7
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON RE-SUBMITTAL OF
 THE ABOVE.
  