| Notes |
| Date |
Text |
| 2016-05-19 16:52:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET D 1 - THERE IS NO INDICATION OF REVIEW OF | | | COMPLAINCE WITH THE FLORIDA FIRE PREVENTION CODE. | | | PLEASE ENSURE COMPALINACE AND PROVIDE A NOTE: | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | | | | 2) SHEET D 1 & A 2 - IS THIS A MIXED OR SEPARATED | | | OCCUPANCY? THE AREA OF THE STORAGE AND THE AREA IN THE | | | FRONT IS BUISNESS/ASSEMBLY AND IS REQUIRED TO BE | | | SEPARATED BY A 2 HOUR FIRE RATING. PLEASE | | | EXPLAIN/JUSTIFY AND/OR PROVIDE SEPARATION PER NFPA 101, | | | CHAPTER 6, 6.1.14.4.1. | | | | | | 3) SHEET A 2 - THE DOOR SCHEDULE DOES NOT INDICATE THE | | | TYP OF HARDWARE FOR DOORS INDICATED AS # 2. PLEASE | | | PROVIDE HARDWARE COMPLIANT WITH NFPA 101, CHAPTER 7, | | | MEANS OF EGRESS, 7.2 | | | | | | 4) SHEET LS 1 - THE REAR EEXIT DOES NOT INDCATE A | | | DISCHARGE TO A PUBLIC WAY. THE AREA IS FENCED. THIS | | | DOES MEET THE REQUIRED EXTING FROM THE STURCTURE PER | | | NFPA 101, CHAPTER 7, MEANS OF EGRESS, 7.7 | | | | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON RE-SUBMITTAL OF | | | THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|