2016-05-12 15:18:12JOB PERMIT NUMBER: 16050444
 JOB ADDRESS: 3234 S DIXIE
 WEST PALM BEACH FLORIDA
 DATE: MAY 12 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING AND EXIT
 SIGNS SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL
 AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA,
 EM LIGHTS MAY BE ON OWN CIRCUIT.
 - C405.2 LIGHTING CONTROLS (MANDATORY). LIGHTING
 SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS SPECIFIED IN
 SECTIONS C405.2.1, C405.2.2, C405.2.3 AND C405.2.4.
 - C405.2.2.2 OCCUPANCY SENSORS.
 - OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL
 CLASSROOMS, CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH
 AND BREAK ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE
 ROOMS AND JANITORIAL CLOSETS, AND OTHER SPACES 300
 SQUARE FEET (28 M2) OR LESS ENCLOSED BY
 FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
 CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY
 TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR
 SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING
 ON TO NOT MORE THAN 50 PERCENT POWER.
 - NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 - NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
 - NEC 210.8(B) GFCI PROTECTION REQUIRED IN BATHROOMS
 AND COUNTERTOP SPACES WITHIN 6? OF A SINK.
 - NEC 300.21 OPENINGS AROUND ELECTRICAL PENETRATIONS
 INTO OR THROUGH FIRE-RESISTANT-RATED WALLS, PARTITIONS,
 FLOORS, OR CEILINGS SHALL BE FIRE STOPPED USING
 APPROVED METHODS TO MAINTAIN THE FIRE RESISTANCE
 RATING.
 - GENERATOR MUST BE SUBMITTED UNDER A SEPARATE PERMIT
 WITH SHOP DRAWINGS WITH MANUFACTURE SPECS ON THE
 EQUIPMENT AND TRANSFER SWITCH.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER