| Notes |
| Date |
Text |
| 2016-05-12 14:19:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET FA 1 - IN THE FIRE ALARM RISER DIAGRAM 10 | | | SMOKE DETECTORS ARE INDICATED. ON SHEET FA 2 - CIRCUIT | | | CALCUATIONS TABLE; 25 SMOKE DETECTORS ARE INDICATED. | | | | | | PLEASE VERIFY AND CORRECT. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|