| 2016-05-19 11:28:29 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| | LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA, |
| | WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. |
| | 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4- |
| | COMPLETION DOCUMENTS PER CODE SECTION. |
| | 3. LABEL MAINS TO INDICATE MAIN 1 OF 2 AND 2 OF 2, FOR |
| | THE 400A SERVICE SHOWN. NEC 230.2 |
| | 4. SHOW ON PANEL BOARD SCHEDULE ALL BRANCH CIRCUIT |
| | CONDUCTOR SIZES. FBC 107.3.5 |
| | 5. LABEL CIRCUIT LA-15 TO BE GFCI PROTECTED FOR THE |
| | DRINKING FOUNTAIN. NEC 422.52 |
| | 6. PLEASE LABEL THE KITCHEN RECEPTACLE OUTLET WITHIN |
| | 6FT OF SINK TO BE GFCI PROTECTED. NEC 210.8B2 AND NOTE |
| | THAT ALL 125V 20A RECEPTACLES WITHIN THE FOOD |
| | PREPARATION AREA TO BE LABELED GFCI ALSO. NEC 210.8B5 |
| | 7. ADDRESS ALL FIRE COMMENTS RELATED TO ELECTRICAL |
| | SHEETS, EXIT LIGHTING, HOOD AND FIRE ALARM DRAWINGS. |
| | 8. PROVIDE A GENERAL NOTE TO INDICATE THE REQUIREMENTS |
| | OF NEC 410.130G1- DISCONNECTING MEANS FOR ALL DOUBLE |
| | ENDED LAMPS. |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |