Plan Review Notes
Plan Review Notes For Permit 16050357
Permit Number 16050357
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-18 13:23:26 
 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16050357
 5/18/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 2) PROVIDE OUTDOOR AIR SHUTOFF DAMPER CONTROLS FOR EACH
 AC SYSTEM IN COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION .
 3) SHEET M02.102: PROVIDE DUCT SMOKE DETECTORS IN THE
 RETURN AIR SYSTEMS OF RTU-2 AND RTU-4.
 4) M02.102: PROVIDE A LABEL TO IDENTIFY RTU-2
 5) M02.102: PROVIDE THE FLEX DUCT SIZES AND CFMS AT ALL
 DIFFUSERS AND RETURN GRILLS.
 6) M02.102: INCLUDE THE FLEX DUCTS IN THE SCHEDULE.
 7) M02.102, NOTE #5: THE EXHAUST CAPACITY IN THE MEN'S
 BATHROOM SHALL BE MINIMUM 100 CFMS UNLESS THE EXHAUST
 WILL RUN CONTINUOUSLY- TABLE 403.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  