| 2016-05-18 13:23:26 | | | | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16050357 | | | 5/18/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | 2) PROVIDE OUTDOOR AIR SHUTOFF DAMPER CONTROLS FOR EACH | | | AC SYSTEM IN COMPLIANCE WITH SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION . | | | 3) SHEET M02.102: PROVIDE DUCT SMOKE DETECTORS IN THE | | | RETURN AIR SYSTEMS OF RTU-2 AND RTU-4. | | | 4) M02.102: PROVIDE A LABEL TO IDENTIFY RTU-2 | | | 5) M02.102: PROVIDE THE FLEX DUCT SIZES AND CFMS AT ALL | | | DIFFUSERS AND RETURN GRILLS. | | | 6) M02.102: INCLUDE THE FLEX DUCTS IN THE SCHEDULE. | | | 7) M02.102, NOTE #5: THE EXHAUST CAPACITY IN THE MEN'S | | | BATHROOM SHALL BE MINIMUM 100 CFMS UNLESS THE EXHAUST | | | WILL RUN CONTINUOUSLY- TABLE 403.3. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|