| Plan Review Notes For Permit 16050357 |
| Permit Number |
16050357 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-17 06:56:06 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PROVISO- ADD A GENERAL NOTE TO INDICATE LOW VOLTAGE | | | SYSTEMS TO BE PERMITTED SEPARATELY, ACCESS, DATA/TEL, | | | FIRE ALARM ETC. | | | 2. CONFIRM CLEARANCE FOR THE NEW PANEL BOARD INSTALLED | | | IN EXISTING ELECTRICAL ROOM. A NOTE WILL SUFFICE NEC | | | 110.26. | | | 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|