Plan Review Notes
Plan Review Notes For Permit 16050357
Permit Number 16050357
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-17 06:56:06INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO- ADD A GENERAL NOTE TO INDICATE LOW VOLTAGE
 SYSTEMS TO BE PERMITTED SEPARATELY, ACCESS, DATA/TEL,
 FIRE ALARM ETC.
 2. CONFIRM CLEARANCE FOR THE NEW PANEL BOARD INSTALLED
 IN EXISTING ELECTRICAL ROOM. A NOTE WILL SUFFICE NEC
 110.26.
 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  