| 2016-05-09 15:40:29 | RESIDENTIAL (R3) BUILDING REVISION COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | NOTE: THE REVISION FEE IS $207. THE ARCHITECTURAL | | | DRAWINGS SUBMITTED ARE APPROVED. THE ENERGY | | | CALCULATIONS NEED TO BE REVISED. REMAINDER: PROVIDE ALL | | | OTHER ITEMS REQUESTED ON PROVISO. SEE ORIGINAL APPROVED | | | PLANS. | | | | | | 1- REVISE ENERGY CALCULATIONS SUBMITTED: | | | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM | | | INCLUDING THE BUILDER NAME, CORRECT PERMIT OFFICE (1212 | | | FLORIDA AVE IS NOT THE PERMIT OFFICE). SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014) | | | | | | B) ADJACENT WALL TYPE AND INSULATION R-VALUE ON ITEM #9 | | | IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014) | | | | | | C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH | | | PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014) | | | | | | | | | IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE | | | U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY | | | CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS | | | ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|