| Plan Review Notes For Permit 16050338 |
| Permit Number |
16050338 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-16 16:57:10 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 3. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW | | | CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO | | | BE DOWN STREAM OF MANUAL VALVE. |
|