| 2016-05-31 15:12:37 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED. |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1) SHEET CS 1 - THERE IS AN INCORRECT REFERENCE TO THE |
| | FIRE CODE. THOUGH IT MAY NOT NEGATIVELY AFFECT THE |
| | SUBMITTAL, IT MAY REQUIRE FURTHER REVIEW FOR |
| | COMPLIANCE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | |
| | |
| | 2) SHEET A 1 - THERE IS A NOTE INDICATING THE |
| | RELOCATION OF A SD AND FA DEVICE. PLEASE PROVIDE A NOTE |
| | AND ENSURE THE FOLLOWING: |
| | |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| | UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |
| | 3) SHEET A 1 - THERE ARE NEW WALLS INDCATED. ANY |
| | REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR CEILINGS |
| | IN A SPRINKLERED BUILDING REQUIRES AN EVALUATION OF THE |
| | SPRINKLER PROTECTION. A CERTIFIED FIRE SPRINKLER |
| | CONTRACTOR SHALL REVIEW THE PROPOSED AND IF REQUIRED, |
| | PROVIDE SHOP DRAWINGS FOR ANY WORK. |
| | |
| | ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE |
| | DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED |
| | LIFE SAFETY CONTRACTOR. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |